Optimization analysis of influencing factors of water mist system in utility tunnel based on orthogonal tests

被引:1
作者
Bai, Zhenpeng [1 ]
Yu, Yueyang [1 ]
Liu, Yueming [1 ]
Qin, Hengjie [1 ]
Yao, Haowei [1 ]
机构
[1] Zhengzhou Univ Light Ind China, Coll Bldg Environm Engn, Dept Zhengzhou Key Lab Elect Power Fire Safety, Zhengzhou, Peoples R China
关键词
Utility tunnel; Cable fire; Numerical simulation; Fire extinguishing effect; Orthogonal test; TEMPERATURE DISTRIBUTION; FIRE; SUPPRESSION;
D O I
10.1016/j.applthermaleng.2025.125814
中图分类号
O414.1 [热力学];
学科分类号
摘要
The utility tunnel is distinguished by its elongated and confined geometry, which exacerbates the rapid propagation of fire in the event of an incident. Minimizing the adverse impact of a power cable fire on the electricity supply to adjacent residents is of utmost importance. In this paper, the orthogonal test method was employed to investigate the sensitivity sequence of four factors influencing fire suppression in utility tunnels, specifically analyzing the suppression efficacy of a fine water mist system on cable fires within utility tunnels. Subsequently, the accuracy of the numerical simulation was validated by comparing with an experimental case study. The results showed that the sensitivity order of the fine water mist system to the temperature of a utility tunnel fire is as follows: nozzle flow coefficient, ventilation conditions, droplet size, and initial droplet velocity. Furthermore, sensitivity analysis unveiled that an optimal combination of these factors can significantly enhance suppression efficiency. Specifically, the optimal combination of fine water mist parameters led to a 64.33 % increase in extinguishing efficiency compared to the average value. Lastly, this paper put forward recommendations to augment the cable compartment fire suppression system, thereby fostering conditions conducive to the safe operation of the cable compartment. The results presented in this paper provide valuable insights for the optimized design of the fine water mist fire suppression system in the cable compartment of utility tunnels, serving as a benchmark for future research endeavors in this domain.
引用
收藏
页数:12
相关论文
共 37 条
[31]  
[许云骅 Xu Yunhua], 2024, [中国给水排水, China Water & Wastewater], V40, P115
[32]  
[杨立中 Yang Lizhong], 2021, [中国安全科学学报, China Safety Science Journal(CSSJ)], V31, P132
[33]   A numerical simulation of the suppression of hydrogen jet fires on hydrogen fuel cell ships using a fine water mist [J].
Yuan, Yupeng ;
Wu, Sifan ;
Shen, Boyang .
INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2021, 46 (24) :13353-13364
[34]   Experimental study on the interaction between fire and water mist in long and narrow spaces [J].
Zhang, Peihong ;
Tang, Xing ;
Tian, Xiangliang ;
Liu, Chang ;
Zhong, Maohua .
APPLIED THERMAL ENGINEERING, 2016, 94 :706-714
[35]   Experimental study on smoke temperature distribution under different power conditions in utility tunnel [J].
Zhao, Yong-chang ;
Zhu, Guo-qing ;
Gao, Yun-ji .
CASE STUDIES IN THERMAL ENGINEERING, 2018, 12 :69-76
[36]   Combustion characteristics and thermal decomposition mechanism of the flame-retardant cable in urban utility tunnel [J].
Zheng, Xuezhao ;
Cai, Guobin ;
Guo, Jun ;
Gao, Wenjing ;
Huang, Yuan ;
Tong, Xin .
CASE STUDIES IN THERMAL ENGINEERING, 2023, 44
[37]   Integrating FBN and FDS for quantitative risk assessment of cable fire in utility tunnel [J].
Zhu, Xiaoping ;
Wu, Jiansong ;
Bai, Yiping ;
Wang, Dong ;
Zhang, Jun .
JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 2024, 88