Optimizing membrane dehumidification performance: A comprehensive review of materials, modules and system

被引:0
|
作者
Liu, Yilin [1 ]
Fan, Junbao [1 ]
Su, Jincai [2 ]
Li, Na [3 ]
Cui, Xin [1 ]
Jin, Liwen [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Human Settlements & Civil Engn, 28 Xianning West Rd, Xian 710049, Peoples R China
[2] Ngee Ann Polytech, Sch Life Sci & Chem Technol, 535 Clementi Rd, Singapore 599489, Singapore
[3] Xi An Jiao Tong Univ, Sch Chem Engn & Technol, 28 West Xianning Rd, Xian 710049, Peoples R China
来源
JOURNAL OF ENVIRONMENTAL CHEMICAL ENGINEERING | 2025年 / 13卷 / 02期
基金
中国国家自然科学基金;
关键词
Membrane dehumidification; Performance optimization; Material modification; Module structure; System integration; HEAT-PUMP DRIVEN; FILM NANOCOMPOSITE MEMBRANES; HOLLOW-FIBER MEMBRANES; FLAT SHEET MEMBRANE; AIR-DEHUMIDIFICATION; MASS-TRANSFER; WATER-VAPOR; COMPOSITE MEMBRANE; LIQUID-MEMBRANES; FLUID-FLOW;
D O I
10.1016/j.jece.2025.115990
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Membrane dehumidification technology has gained significant attention for its efficiency, energy savings, and simplicity. Enhancing the performance of membrane dehumidification is crucial as it directly impacts energy efficiency and indoor comfort, promoting wider adoption of this innovative approach. Significant advances have been made in enhancing membrane dehumidification performance from the perspectives of materials, modules, and systems. This review delves into recent developments, focusing on enhancement methods, dehumidification effects, and limitations. Innovations in membrane materials, such as the use of nanoparticles and hydrophilic functional groups, improve permeability, selectivity, and durability. Moreover, novel module designs, like porous or spiral-wound configurations, increase the surface area and optimize flow dynamics, thereby boosting the dehumidification efficiency. Connecting multiple modules in series or parallel enhances performance but introduces manufacturing complexities, higher flow resistance, and fouling risks. At the system level, integrating membranes with heat recovery or renewable energy systems can reduce energy consumption by over 20 % compared to traditional methods. In this review, the optimization recommendations for membrane materials, modules, and systems were proposed. Combining molecular-scale modeling with experimental testing provides a precise path for upgrading membrane properties. The mass transfer characteristics within modules, along with multi-objective optimization, support a more efficient and rational design of the membrane module. Additionally, the exergy analysis can identify energy-intensive areas, refining the system design strategies for greater efficiency.
引用
收藏
页数:34
相关论文
共 50 条
  • [1] Energy performance analysis of a membrane dehumidification system
    Bynum, John D.
    Claridge, David E.
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 127 : 230 - 238
  • [2] Isothermal membrane-based air dehumidification: A comprehensive review
    Qu, Ming
    Abdelaziz, Omar
    Gao, Zhiming
    Yin, Hongxi
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 82 : 4060 - 4069
  • [3] Investigation of dehumidification performance and flow characteristics of wavy vacuum membrane-based dehumidification modules
    Chun, Liang
    Gong, Guangcai
    Fang, Xi
    Peng, Pei
    Li, Wenqiang
    CHEMICAL ENGINEERING RESEARCH & DESIGN, 2021, 167 : 292 - 302
  • [4] Membrane-based liquid desiccant air dehumidification: A comprehensive review on materials, components, systems and performances
    Liu, Xiaoli
    Qu, Ming
    Liu, Xiaobing
    Wang, Lingshi
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2019, 110 : 444 - 466
  • [5] Performance characteristics of a novel internally-cooled plate membrane liquid desiccant air dehumidification system
    Xiao, Liehui
    Yang, Minlin
    Yuan, Wu-Zhi
    Huang, Si-Min
    APPLIED THERMAL ENGINEERING, 2020, 172
  • [6] DEHUMIDIFICATION PERFORMANCE INVESTIGATION OF RUN-AROUND MEMBRANE ENERGY EXCHANGER SYSTEM
    Kassai, Miklos
    Ge, Gaoming
    Simonson, Carey J.
    THERMAL SCIENCE, 2016, 20 (06): : 1927 - 1938
  • [7] Membrane-based air dehumidification: A comparative review on membrane contactors, separative membranes and adsorptive membranes
    Lim, Huaixun
    Goh, Kunli
    Tian, Miao
    Wang, Rong
    CHINESE JOURNAL OF CHEMICAL ENGINEERING, 2022, 41 : 121 - 144
  • [8] Performance Investigation of a Hollow Fiber Membrane-Based Desiccant Liquid Air Dehumidification System
    Englart, Sebastian
    Rajski, Krzysztof
    ENERGIES, 2021, 14 (11)
  • [9] Performance testing of a cross-flow membrane-based liquid desiccant dehumidification system
    Bai, Hongyu
    Zhu, Jie
    Chen, Ziwei
    Ma, Lina
    Wang, Ruzhu
    Li, Tingxian
    APPLIED THERMAL ENGINEERING, 2017, 119 : 119 - 131
  • [10] Size effects of carboxylated magnetite nanoparticles on the membrane dehumidification performance
    Abou-Elanwar, Ali M.
    Shirke, Yogita M.
    Kwon, Soon Jin
    Choi, Won-Kil
    Hong, Seong Uk
    Lee, Hyung Keun
    Jeon, Jae-Deok
    JOURNAL OF ENVIRONMENTAL CHEMICAL ENGINEERING, 2021, 9 (04):