Studies of a Mechanically Pumped Two-Phase Loop with a Pressure-Controlled Accumulator Under Pulsed Evaporator Heat Loads

被引:0
作者
Truster, Nicholas [1 ]
Ervin, Jamie S. [2 ]
Roman, Abdeel [1 ]
Monfort, Jeff [3 ]
机构
[1] Air Force Res Lab, 2450 D St Bldg 20, Wright Patterson AFB, OH 45433 USA
[2] Univ Dayton, Dept Mech & Aerosp Engn, 300 Coll Pk, Dayton, OH 45469 USA
[3] Univ Dayton, Res Inst, Dept Mech & Aerosp Engn, 300 Coll Pk, Dayton, OH 45469 USA
关键词
two-phase flow; aircraft environmental control; mechanically pumped two-phase loop; pressure-controlled accumulator; PERFORMANCE;
D O I
10.3390/en17246347
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
As avionics become more power dense, electronic device cooling has become a significant barrier to aircraft integration. A mechanically pumped two-phase loop (MPTL) is a thermal subsystem that enables near isothermal evaporator operation, which is desirable for electronics cooling. The goal of this study was to integrate an MPTL with a pressure-controlled accumulator and model a predictive control technique to demonstrate improvements for transient, isothermal evaporator operation for MPTLs under pulsed evaporator heat loads. The model predictive controller enables active control of MPTL compressible volume, which has not been demonstrated for pulsed evaporator heat loads. Experimental data were collected to validate a representative numerical model. A pressure-controlled accumulator was added to an MPTL to experimentally characterize the system thermodynamic response for three pulsed evaporator heat loads. Two statistical methods were used to assess the numerical model agreement with the experimental results. Under pulsed evaporator heat loads, the mean percent error agreed within 3.45% and the mean average percent error agreed within 0.74% for the three pulsed evaporator heat loads. Finally, a traditional proportional-integral (PI) controller and an advanced model predictive controller were developed and integrated into the validated numerical model. Both control methods were evaluated for an expanded set of evaporator heat load profiles to analyze transient behavior. For evaporator heat profiles with high heat transfer rates, the model predictive controller can maintain a target +/- 2 K refrigerant temperature at the evaporator exit throughout the evaporator heat load duration, whereas the PI-controlled MPTL cannot. Through this work, active control of a pressure-controlled accumulator within an MPTL is shown to improve refrigerant isothermal (+/- 2 K) operation when compared to a traditional control technique.
引用
收藏
页数:20
相关论文
共 36 条
[1]  
[Anonymous], 2023, MathWorks Optimization Problem
[2]  
[Anonymous], 2011, MathWorks Quantization, Projection, and Pruning
[3]  
Bergman T.L., 2011, Introduction to heat transfer, DOI DOI 10.1016/J.APPLTHERMALENG.2011.03.022
[4]   Improved correlation for predicting heat transfer coefficients during condensation inside smooth horizontal tubes [J].
Blose, Sibongakonke C. ;
Ewim, Daniel R. E. ;
Eloka-Eboka, Andrew C. ;
Adelaja, Adekunle O. .
INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2023, 18 :750-763
[5]  
Calabrese S.R., 2003, Practical Controls: A Guide to Mechanical Systems, P19
[6]  
Carey V.P., 2020, Liquid-vapor phase-change phenomena: an introduction to the thermophysics of vaporization and condensation processes in heat transfer equipment
[7]   Numerical analysis of pumped two-phase loop: Characterization of steady-state performance [J].
Kokate, Rohan ;
Park, Chanwoo .
APPLIED THERMAL ENGINEERING, 2023, 229
[8]   Effects of flow loop compressible volume position on system instabilities during flow boiling in micro-channel heat sinks [J].
Lee, Jeongmin ;
Devahdhanush, V. S. ;
Darges, Steven J. ;
Mudawar, Issam .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2022, 198
[9]   Thermal control of a mechanically pumped two-phase loop [J].
Li, Guanru ;
Jiang, Haitao ;
Zheng, Yi ;
Zhang, Chengbin .
INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2022, 138
[10]   Experimental Study on the Dynamic Heat Transfer Characteristics of a Mechanically Pumped Two-phase Cooling Loop [J].
Li, Lei ;
Tao, Jianyun ;
Gao, Wei .
FRONTIERS IN ENERGY RESEARCH, 2021, 9 (09)