Joint optimization of cooling parameters and workload distributions based on model predictive control for rack-based data centers

被引:0
作者
Wang, Jiaqiang [1 ,2 ,3 ]
Deng, Weiqi [1 ,2 ,3 ]
Yue, Chang [1 ]
Su, Wen [1 ]
Bai, Xuelian [4 ]
机构
[1] Cent South Univ, Sch Energy Sci & Engn, Changsha 410083, Hunan, Peoples R China
[2] Anhui Jianzhu Univ, Anhui Prov Key Lab Intelligent Bldg & Bldg Energy, Hefei 230022, Anhui, Peoples R China
[3] Hunan Prov Key Lab Low Carbon Hlth Bldg, Changsha 410083, Hunan, Peoples R China
[4] Chongqing Univ, Sch Civil Engn, Chongqing 400045, Peoples R China
来源
JOURNAL OF BUILDING ENGINEERING | 2025年 / 100卷
基金
中国国家自然科学基金;
关键词
Rack-based cooling data center; State-space model; Cooling parameters; Workload distributions; Joint optimization; PERFORMANCE; MANAGEMENT; SYSTEM;
D O I
10.1016/j.jobe.2025.111801
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
To satisfy the thermal environment requirements, approximately 40 % of energy consumption is used for cooling in data centers. The efficient cooling system and workload management can improve heat dissipation, thereby reducing energy consumption. This paper introduced a novel joint optimization strategy (JOS) for cooling parameters and workload distributions designed for rack-based cooling data centers. The primary objective is to improve overall energy efficiency while ensuring the safe operation of the data center. The proposed strategy considers the thermal interaction between information technology (IT) equipment and cooling devices, as well as the heterogeneity among different servers, achieving granular optimization of cooling parameters and workload distributions. The impacts of different cooling parameters optimization on the energy management and thermal management performance were analyzed. The energy-saving potential and temperature field control effect considering server heterogeneity for the proposed JOS were investigated. The results show that, compared to univariate optimization, simultaneous optimization of supplied cold air temperature and airflow rate can achieve at least 4.7 % in energy-saving. Furthermore, compared with independent control of the cooling system, the proposed JOS effectively addresses server overcooling, achieving a more uniform temperature distribution and further reducing the cooling energy consumption by 5 %. It is noteworthy that the strategy demonstrates high computational efficiency while ensuring energy efficiency.
引用
收藏
页数:18
相关论文
共 42 条
  • [41] Zhu H, 2015, IEEE INTL CONF CONTR, P336, DOI 10.1109/CCA.2015.7320651
  • [42] An advanced control strategy for optimizing the operation state of chillers with cold storage technology in data center
    Zhu, Yiqun
    Zhang, Quan
    Zeng, Liping
    Wang, Jiaqiang
    Zou, Sikai
    Zheng, Haoran
    [J]. ENERGY AND BUILDINGS, 2023, 301