A Theoretical and Test Analysis of Heat and Humidity Transfer for Deeply Buried Underground Corridors with Different Shapes

被引:0
作者
Ren, Tong [1 ]
Li, Mengzhuo [1 ]
He, Long [1 ]
Wang, De [1 ]
Kong, Lingbo [1 ]
机构
[1] Shaanxi Univ Sci & Technol, Coll Mech & Elect Engn, Xian 710021, Peoples R China
基金
中国国家自然科学基金;
关键词
underground corridor; corridor shape; heat and humidity transfer; field test; mathematical model; TUNNEL;
D O I
10.3390/en18020234
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Moisture generation in the ventilation projects of deeply buried underground corridors affects the underground building environment and personnel health. In order to master the heat and humidity transfer law of underground corridors, this paper establishes a mathematical model by theoretical analysis, and the application of the theoretical model in engineering calculation is verified by a field test. It is found that the ventilation efficiency and heat and humidity transfer effect are related to corridor shape. The results show that under the same cross-sectional area, the average temperature drop and humidity of a rectangular corridor are 0.25% and 0.3% higher than that of an arch corridor, and 0.8% and 0.9% higher than that of a circular corridor. Under the condition of constant section circumference, the average temperature drop and humidity of a rectangular corridor are 0.51% and 0.62% higher than that of an arch corridor, and 1.37% and 1.58% higher than that of a circular corridor. When the equivalent diameter is the same, there is almost no difference in the heat and humidity transfer effect of the three shaped corridors.
引用
收藏
页数:24
相关论文
共 38 条
[1]  
[Anonymous], 2014, Seminar Presentation of HVAC Cooling Load Calculation, P1
[2]  
Chen Q.G., 1984, J. Civ. Environ. Eng, V3, P1
[3]  
Chen Q.G., 1980, J. Refrig, V3, P30
[4]  
Chen S.S., 2013, Prot. Eng, V35, P73
[5]   A one-dimensional transient analytical model for earth-to-air heat exchangers, taking into account condensation phenomena and thermal perturbation from the upper free surface as well as around the buried pipes [J].
Cucumo, M. ;
Cucumo, S. ;
Montoro, L. ;
Vulcano, A. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2008, 51 (3-4) :506-516
[6]  
[戴理韬 Dai Litao], 2020, [电力系统自动化, Automation of Electric Power Systems], V44, P169
[7]  
Dang Y.R., 2012, Masters Thesis
[8]   EFFECT OF DEPTH OF SINKING ON THERMAL PERFORMANCE OF PARTIALLY UNDERGROUND BUILDING [J].
DESHMUKH, MK ;
SODHA, MS ;
SAWHNEY, RL .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1991, 15 (05) :391-403
[9]  
Eckert E.R., 1983, Analysis of Heat and Mass Transfer, VVolume 845
[10]   Utilizing Wastewater Tunnels as Thermal Reservoirs for Heat Pumps in Smart Cities [J].
Fadnes, Fredrik Skaug ;
Assadi, Mohsen .
ENERGIES, 2024, 17 (19)