Experimental investigation on the low temperature performance of a novel three-pressure air source heat pump

被引:0
作者
Bai, Jing [1 ]
Wang, Lejian [1 ]
Cui, Siqi [1 ]
Zheng, Huifan [1 ]
He, Siyuan [1 ]
Chen, Mingzhi [1 ]
机构
[1] Zhongyuan Univ Technol, Sch Energy & Environm, Zhengzhou 450007, Peoples R China
基金
中国国家自然科学基金;
关键词
Three-pressure; Air source heat pump; Heating; Defrosting; SYSTEMS; GROWTH;
D O I
10.1016/j.applthermaleng.2024.124628
中图分类号
O414.1 [热力学];
学科分类号
摘要
As people's demand for living comfort grows, the problems of conventional air source heat pumps (ASHPs) become more prominent in low-temperature and high-humidity environments: heating performance attenuation, low defrosting efficiency, and significant impact on indoor thermal comfort during defrosting. Existing literature usually focuses on only one or two of these issues, and few comprehensively cover them. Based on current literature, this paper proposes a novel multi-functional three-pressure ASHP that can cover the above three aspects with a series-parallel combination structure featuring dual compressors and dual cycles. This design enables switching multiple heating and defrosting modes through valve combination and improves performance through two-stage throttling and subcooling. An experimental platform is constructed to evaluate its operational performance. The experimental results show that: (1) In heating modes, the average heating capacity of the three-pressure cycle heating mode is 2897.15 W, and the average COP is 2.47, while these two data of the conventional cycle heating mode are 2393.65 W and 2.4, and the improvement rates of 20.4 % and 2.9 %, respectively. It also extends the high-efficiency heating period of the system, enables rapid heating at start-up, increases compressor suction and discharge pressure, and improvs system stability. (2) In defrosting modes, compared with the conventional defrosting cycle, the three-pressure defrosting cycle raises the condensation temperature faster, reduces the defrosting time from 448 s to 265 s (40.8 % shorter). The auxiliary defrosting cycle has little effect on indoor thermal comfort and less defrosting power consumption, with the power saving rate as high as 44.6 %. Overall, the novel three-pressure ASHP has a unique and innovative structure, significantly optimizing performance under low-temperature and frosting conditions and improving energy efficiency and comfort. The results of this study provide a new solution concept for the future development of ASHPs, offering significant reference value for further development and application.
引用
收藏
页数:13
相关论文
共 50 条
  • [31] An experimental investigation on reverse-cycle defrosting performance for an air source heat pump using an electronic expansion valve
    Qu, Minglu
    Xia, Liang
    Deng, Shiming
    Jiang, Yiqiang
    [J]. APPLIED ENERGY, 2012, 97 : 327 - 333
  • [32] A flexible and low cost experimental stand for air source heat pump for Smart Buildings
    Craciun, Vasile S.
    Bojesen, Carsten
    Blarke, Morten B.
    Trifa, Viorel
    [J]. PROCEEDINGS OF THE 13TH INTERNATIONAL CONFERENCE ON OPTIMIZATION OF ELECTRICAL AND ELECTRONIC EQUIPMENT, VOLS 1-5, 2012, : 1040 - 1045
  • [33] Experimental research on a novel frost-free air source heat pump system
    Qiu J.
    Zhang X.
    Li W.
    [J]. Huagong Xuebao/CIESC Journal, 2019, 70 (04): : 1605 - 1613
  • [34] Experimental study on performance optimization of air source heat pump using DOE method
    Fang, Zhaosong
    Feng, Xiwen
    Zheng, Zhimin
    Zhou, Xiaoqing
    Li, Li
    Huang, Yu
    Wang, Huan
    Liu, Fengjiao
    [J]. EXPERIMENTAL HEAT TRANSFER, 2019, 32 (03) : 267 - 283
  • [35] Experimental study on frost growth and dynamic performance of air source heat pump system
    Guo, Xian-Min
    Chen, Yi-Guang
    Wang, Wei-Hua
    Chen, Chun-Zheng
    [J]. APPLIED THERMAL ENGINEERING, 2008, 28 (17-18) : 2267 - 2278
  • [36] Experiment study on performance of air source heat pump
    Shi, Weixiu
    Pan, Lisheng
    [J]. ENERGY AND POWER TECHNOLOGY, PTS 1 AND 2, 2013, 805-806 : 645 - +
  • [37] An Experimental Study on External Ventilation to the Heating Performance of Household Air Source Heat Pump
    Zou, Hang
    Liu, Zhanqiang
    Long, Enshen
    [J]. FRONTIERS IN ENERGY RESEARCH, 2021, 9
  • [38] Experimental study on frost growth and dynamic performance of air source heat pump system
    Guo, X. M.
    Chen, Y. G.
    Wang, W. H.
    Chen, C. Z.
    [J]. CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 476 - 482
  • [39] Air source heat pump in-situ performance
    Chesser, Michael
    Lyons, Padraig
    O'Reilly, Padraic
    Carroll, Paula
    [J]. ENERGY AND BUILDINGS, 2021, 251
  • [40] Performance Investigation of An Air Source Heat Pump for Residential Heat Supply Through PCM Underfloor Heating
    Huang, Ming Jun
    Hewitt, Neil J.
    [J]. PROCEEDINGS OF THE ISES SOLAR WORLD CONFERENCE 2019 AND THE IEA SHC SOLAR HEATING AND COOLING CONFERENCE FOR BUILDINGS AND INDUSTRY 2019, 2019, : 1763 - 1771