Design of On-Site Calibration Device for Electricity Meter Based on Pulse Detection

被引:0
|
作者
Wang, Yingchun [1 ]
Yu, Wenjing [1 ]
Zhang, Cheng [1 ]
Ye, Li [1 ]
Wei, Wei [1 ]
Yang, Zhixin [2 ]
机构
[1] State Grid Hubei Elect Power Co Mkt Serv Ctr Measu, Wuhan 430074, Peoples R China
[2] Shenzhen CLOU Elect Co Ltd, Shenzhen 518057, Peoples R China
关键词
electricity energy meter; on-site calibration; optimal frequency estimation; lock-frequency synchronous sampling; digital to frequency; electric energy pulse;
D O I
10.3390/inventions10010006
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
At present, the error calibration of electricity meters in operation generally adopts an off-site method; that is, the electricity meter is taken out of operation and then calibrated in the laboratory. Off-site calibration, while beneficial, may not fully capture the operational error of the electricity meter due to potential differences in environmental conditions. An on-site calibration device for electricity meters based on pulse detection is designed, which obtains the error of the electricity meter under calibration by comparing the energy pulses of the standard electricity meter with those of the electricity meter under calibration. High-precision voltage and current sampling channels are designed, with a voltage measurement error of less than 0.02% and a current measurement error of less than 0.03%. In response to the non-synchronous sampling problem caused by frequency fluctuations in the on-site verification environment, a fast optimal frequency estimation algorithm is applied to accurately calculate the signal frequency within two cycles. The sampling time interval is adjusted to achieve lock-frequency synchronous sampling, and ensure the accurate calculation of electrical parameters. In order to reduce the complexity of the device circuit structure and equipment cost, a standard electric energy pulses generation method based on digital integration-to-frequency is proposed, which uses software to generate electric energy pulses, with a maximum output frequency of up to 10 kHz. Tests conducted in the laboratory on the developed on-site calibration device for electricity meters show that its accuracy is better than the 0.05 accuracy class, meeting the application requirements for on-site verification of electricity energy meters.
引用
收藏
页数:9
相关论文
共 9 条
  • [1] An Improved Design of the MultiCal On-Site Calibration Device for Industrial Robots
    Wan, Ziwei
    Zhou, Chunlin
    Lin, Zhaohui
    Yan, Huapeng
    Tang, Weixi
    Wang, Zhen
    Wu, Jun
    SENSORS, 2023, 23 (12)
  • [2] Development and application verification of on-site calibration device for photogrammetry system
    Ou, Jia
    Xu, Tingfa
    Qu, Jiansu
    Li, Yang
    AOPC 2023:OPTIC FIBER GYRO, 2023, 12968
  • [3] An On-site calibration method for on-line detection system of wheelset geometric parameters
    Tu, YiMeng
    He, Qixin
    Ran, Yunfeng
    Feng, Qibo
    2019 INTERNATIONAL CONFERENCE ON OPTICAL INSTRUMENTS AND TECHNOLOGY: OPTOELECTRONIC MEASUREMENT TECHNOLOGY AND SYSTEMS, 2020, 11439
  • [4] A Novel Multifeature Based On-Site Calibration Method for LiDAR-IMU System
    Liu, Wanli
    Li, Zhixiong
    Malekian, Reza
    Angel Sotelo, Miguel
    Ma, Zhenjun
    Li, Weihua
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2020, 67 (11) : 9851 - 9861
  • [5] Investigation on Motor-driving Maize Precision Seed Meter System Supporting On-site Calibration of Rotate Speed of Seed Plate
    Yang S.
    Wang X.
    Gao Y.
    Zhai C.
    Zhao X.
    Zhao C.
    Nongye Jixie Xuebao/Transactions of the Chinese Society for Agricultural Machinery, 2020, 51 (01): : 47 - 55
  • [6] HP3-RAD: A compact radiometer design with on-site calibration for in-situ exploration
    Kopp, Emanuel
    Mueller, Nils
    Grott, Matthias
    Walter, Ingo
    Knollenberg, Joerg
    Haenschke, Frank
    Kessler, Ernst
    Meyer, Hans-Georg
    INFRARED REMOTE SENSING AND INSTRUMENTATION XXIV, 2016, 9973
  • [7] A fast on-site calibration method designed based on hierarchical coupled discrete mathematical model
    Wang Zemin
    Xie Mengtao
    Lei Zhiyong
    Gao Junchai
    JOURNAL OF DIFFERENCE EQUATIONS AND APPLICATIONS, 2017, 23 (1-2) : 429 - 442
  • [8] On-Site Calibration-Based Estimation Method of Forward Seabed Elevation Using Forward Scan Sonar
    Pyo, Juhyun
    Cho, Hyeonwoo
    Yu, Son-Cheol
    IEEE SENSORS JOURNAL, 2019, 19 (19) : 8832 - 8844
  • [9] On-Site Calibration Method for Line-Structured Light Sensor-Based Railway Wheel Size Measurement System
    Ran, Yunfeng
    He, Qixin
    Feng, Qibo
    Cui, Jianying
    SENSORS, 2021, 21 (20)