Power quality; Distribution networks; Active distribution networks; Partitioning algorithms; Clustering algorithms; Voltage control; Prevention and mitigation; Optimization models; Microgrids; Indexes; Smoothing methods; DERs; DVRs; distribution network partitioning; Kernel smoothing function; short-term voltage fluctuations; voltage sag;
D O I
10.1109/ACCESS.2024.3476242
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The growing emphasis on power quality has posed significant challenges for distribution system operators (DSOs). Among these challenges, short-term voltage fluctuations, specifically voltage sag, have drawn considerable attention. In this study, three concepts of average edge (AE), lower average edge (LAE), and upper average edge (UAE) based on the electrical connection matrix and voltage-magnitude sensitivity matrix are defined and used as the partitioning first level. At the second level, a kernel smoothing function is employed to refine the zoning process. Subsequently, strategic locations within each zone are identified: the vertex and middle buses. These carefully selected buses serve as installation points for dynamic voltage restorers (DVRs). In response, this study proposes a novel solution by partitioning the distribution network into distinct zones. The focus lies in developing a two-level offline partitioning approach for active distribution networks (ADNs) that incorporate photovoltaic (PV) systems. To evaluate the effectiveness of the proposed method, numerical studies were conducted on modified IEEE 33-bus, IEEE 69-bus, and Iranian 95-bus systems, with simulations performed using MATLAB/Simulink. The proposed method provides good performance and fast calculation speed for distribution network partitioning, as confirmed by the results. Test results show improved bus voltage with PV unit integration. Additionally, power loss in the IEEE 33-bus, IEEE 69-bus, and Iranian 95-bus networks decreased by 47.73 kW, 56.87 kW, and 69.63 kW, respectively. Furthermore, the voltage profile improved from 0.75 p.u. to 0.928 p.u. during a voltage sag in the IEEE 33-bus system, and in steady state, the voltage increased from 0.933 to 0.959 p.u.
引用
收藏
页码:149206 / 149220
页数:15
相关论文
共 31 条
  • [1] A new method for evaluation of harmonic distortion in reconfiguration of distribution network
    Amini, MohamadAli
    Jalilian, Alireza
    Behbahani, Milad Rahimi Pour
    [J]. INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2020, 30 (06)
  • [2] [Anonymous], 2019, 11592019 IEEE
  • [3] A Novel Two-Stage Partitioning Based Reconfiguration Method for Active Distribution Networks
    Bansal, Yashasvi
    Sodhi, Ranjana
    Chakrabarti, Saikat
    Sharma, Ankush
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (06) : 4004 - 4016
  • [4] Chance-Constrained Optimal Distribution Network Partitioning to Enhance Power Grid Resilience
    Biswas, Shuchismita
    Singh, Manish K.
    Centeno, Virgilio A.
    [J]. IEEE ACCESS, 2021, 9 : 42169 - 42181
  • [5] Fast unfolding of communities in large networks
    Blondel, Vincent D.
    Guillaume, Jean-Loup
    Lambiotte, Renaud
    Lefebvre, Etienne
    [J]. JOURNAL OF STATISTICAL MECHANICS-THEORY AND EXPERIMENT, 2008,
  • [6] Network Partition and Voltage Coordination Control for Distribution Networks With High Penetration of Distributed PV Units
    Chai, Yuanyuan
    Guo, Li
    Wang, Chengshan
    Zhao, Zongzheng
    Du, Xiaofeng
    Pan, Jing
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2018, 33 (03) : 3396 - 3407
  • [7] Da Lin, 2019, 2019 IEEE Sustainable Power and Energy Conference (iSPEC). Proceedings, P1252, DOI 10.1109/iSPEC48194.2019.8974930
  • [8] [窦晓波 Dou Xiaobo], 2018, [电力系统自动化, Automation of Electric Power Systems], V42, P21
  • [9] Duan R. C., 2015, 2015 IEEE Power & Energy Society General Meeting, P1, DOI 10.1109/PESGM.2015.7286079
  • [10] Intelligent Partitioning in Distributed Optimization of Electric Power Systems
    Guo, Junyao
    Hug, Gabriela
    Tonguz, Ozan K.
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2016, 7 (03) : 1249 - 1258