Technoeconomic Feasibility of Wind and Solar Generation for Off-Grid Hyperscale Data Centres

被引:0
作者
Rollinson, William [1 ]
Urquhart, Andrew [1 ]
Thomson, Murray [1 ]
机构
[1] Loughborough Univ, CREST Ctr Renewable Energy Syst Technol, Wolfson Sch Mech Elect & Mfg Engn, Ashby Rd, Loughborough LE11 3TU, England
关键词
data centre; renewable energy; solar; wind; battery storage; microgrid;
D O I
10.3390/en18020382
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
As a global community our use of data is increasing exponentially with emerging technologies such as artificial intelligence (AI), leading to a vast increase in the energy demand for data centres worldwide. Delivering this increased energy demand is a global challenge, which the rapid growth of renewable generation deployment could solve. For many data centre giants such as Google, Amazon, and Microsoft this has been the solution to date via power purchase agreements (PPAs). However, insufficient investment in grid infrastructure globally has both renewable generation developers and data centre developers facing challenges to connect to the grid. This paper considers the costs and carbon emissions associated with stand-alone hybrid renewable and gas generation microgrids that could be deployed either before a grid connection is available, or to allow the data centre to operate entirely off-grid. WindPRO 4.0 software is used to find optimal configurations with wind and solar generation, backed up by battery storage and onsite gas generation. The results show that off-grid generation could provide lower cost and carbon emissions for each of Europe's data centre hotspots in Frankfurt, London, Amsterdam, Paris, and Dublin. This paper compares each generation configuration to grid equivalent systems and an onsite gas-only generation solution. The results showed that each hybrid renewable generation configuration had a reduced levelized cost of energy (LCOE) and reduced CO2eq emissions compared to that of its grid and gas-only equivalent. Previous literature does not consider the economic implications caused by a mismatch between generation and consumption. Therefore, this paper introduces a new metric to evaluate and compare the economic performance of each microgrid, the levelized cost of energy utilised (LCOEu) which gives the levelized cost of energy for a given microgrid considering only the energy which is consumed by the data centre. The LCOEu across all sites was found to be between 70 and 102 GBP/MWh with emissions between 0.021 and 0.074 tCO2eq/MWh.
引用
收藏
页数:20
相关论文
共 43 条
  • [1] Alsema E, 2012, PRACTICAL HANDBOOK OF PHOTOVOLTAICS: FUNDAMENTALS AND APPLICATIONS, 2ND EDITION, P1097
  • [2] Amazon E., 2015, AMAZON WEB SERVICES
  • [3] Andrae A. S. G., 2015, challenges, V6, P117, DOI [DOI 10.3390/CHALLE6010117, 10.3390/challe6010117]
  • [4] [Anonymous], 2022, Savills Global Farmland Index
  • [5] [Anonymous], 2024, Mobile Fact Sheet
  • [6] [Anonymous], 2023, Google Environmental Report 2023
  • [7] app.electricitymaps, Electricity Maps
  • [8] atb.nrel, NREL Utility-Scale Battery Storage
  • [9] Augustine C., 2021, Input Data Report
  • [10] CBRE, 2023, Global Data Center Trends 2023