Model-Free Optimal Volt-VAR Control of Wind Farm Based on Data-Driven Lift-Dimension Linear Power Flow

被引:0
作者
Guo, Li [1 ]
Liu, Zhaoning [1 ]
Wang, Zhongguan [1 ]
Li, Xialin [1 ]
Liu, Yixin [1 ]
Zhang, Yuxuan [1 ]
Zang, Xiaodi [1 ]
Wang, Chengshan [1 ]
机构
[1] Tianjin Univ, Sch Elect & Informat Engn, Tianjin 300072, Peoples R China
基金
中国国家自然科学基金;
关键词
Voltage control; Wind farms; Reactive power; Load flow; Sensitivity; Mathematical models; Training; Date-driven; power flow; reactive power; sensitivity; voltage control; wind power generation; INTEGRATION;
D O I
10.17775/CSEEJPES.2022.00500
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper proposes a reactive power and voltage optimal control method for wind farms based on data-driven power flow. Because no prior knowledge of wind farm parameters is necessary, the proposed method is model-free. Based on Koopman operator-based method, this paper constructs a power flow model of wind farms connected to the grid by using state space mapping and lift-dimension linearization. Considering reactive power devices such as wind turbines and static var generator (SVG) in wind farms, a global sensitivity-based reactive power and voltage linear optimization control model is proposed. Taking minimum reactive power adjustment of wind turbines and SVG as the objective function, combined with the sensitivity relationship between node voltage and reactive power injection, the proposed model-free voltage control method can realize optimal reactive power distribution, effectively reduce active power loss, and satisfy the requirement of rapid voltage control response of wind farms. Based on historical data of a wind farm in Ningxia, feasibility of the proposed voltage optimal control method under inaccurate parameters is verified. Compared with model-based methods, the proposed method exhibits advantages on parameter dependency and efficiency.
引用
收藏
页码:91 / 101
页数:11
相关论文
共 25 条
[1]   Sensitivity-Analysis-Based Sliding Mode Control for Voltage Regulation in Microgrids [J].
Aghatehrani, Rasool ;
Kavasseri, Rajesh .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2013, 4 (01) :50-57
[2]   Determine Q-V Characteristics of Grid-Connected Wind Farms for Voltage Control Using a Data-Driven Analytics Approach [J].
Andalib-Bin-Karim, Chowdhury ;
Liang, Xiaodong ;
Khan, Nahidul ;
Zhang, Huaguang .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2017, 53 (05) :4162-4175
[3]   Analysis of Voltage Control Strategies for Wind Farms [J].
Asadollash, Shahab ;
Zhu, Rongwu ;
Liserre, Marco .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2020, 11 (02) :1002-1012
[4]   Data-Driven Sensitivity Coefficients Estimation for Cooperative Control of PV Inverters [J].
da Silva, Emanoel Leite ;
Nogueira Lima, Antonio Marcus ;
de Rossiter Correa, Mauricio Beltrao ;
Vitorino, Montie Alves ;
Barbosa, Luciano Tavares .
IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (01) :278-287
[5]  
google, Original data of training samples
[6]   Data-Driven Power Flow Calculation Method: A Lifting Dimension Linear Regression Approach [J].
Guo, Li ;
Zhang, Yuxuan ;
Li, Xialin ;
Wang, Zhongguan ;
Liu, Yixin ;
Bai, Linquan ;
Wang, Chengshan .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2022, 37 (03) :1798-1808
[7]   Online Optimal Feedback Voltage Control of Wind Farms: Decentralized and Asynchronous Implementations [J].
Guo, Yifei ;
Gao, Houlei ;
Wang, Dong ;
Wu, Qiuwei .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2021, 12 (02) :1489-1492
[8]   Distributed Online Voltage Control for Wind Farms Using Generalized Fast Dual Ascent [J].
Guo, Yifei ;
Gao, Houlei ;
Wang, Zhaoyu .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2020, 35 (06) :4505-4517
[9]   STATCOM impact study on the integration of a large wind farm into a weak loop power system [J].
Han, Chong ;
Huang, Alex Q. ;
Baran, Mesut E. ;
Bhattacharya, Subliashish ;
Litzenberger, Wayne ;
Anderson, Loren ;
Johnson, Anders L. ;
Edris, Abdel-Aty .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2008, 23 (01) :226-233
[10]   Distributed Optimal Voltage Control for VSC-HVDC Connected Large-Scale Wind Farm Cluster Based on Analytical Target Cascading Method [J].
Huang, Sheng ;
Wu, Qiuwei ;
Zhao, Jin ;
Liao, Wu .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2020, 11 (04) :2152-2161