Optimal Placement of Phasor Measurement Unit System on the Hungarian Transmission Network

被引:0
|
作者
Galo, Andras [1 ]
Farkas, Csaba [2 ]
Gregus, Zoltan [3 ]
机构
[1] Budapest Univ Technol & Econ, Dept Elect Power Engn, Budapest, Hungary
[2] MAVIR Ltd, Operat Secur Dev Dept, Budapest, Hungary
[3] MAVIR Ltd, Secondary Syst Serv, Budapest, Hungary
来源
9TH INTERNATIONAL YOUTH CONFERENCE ON ENERGY, IYCE 2024 | 2024年
关键词
PMU; Phasor Measurement Unit; optimal placement; Hungarian transmission system; integer linear programming; UCTE data exchange format;
D O I
10.1109/IYCE60333.2024.10634945
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Traditional Supervisory Control and Data Acquisition (SCADA) systems face significant challenges in accurately measuring dynamic changes in power systems, owing to their limited sampling rates and lack of time synchronization. Phasor Measurement Units (PMUs), with their high sampling rates (30-60 Hz) and GPS synchronization, offer a superior alternative for real-time monitoring and simplified state estimation. This study introduces a novel optimization algorithm designed to determine the optimal placement of PMUs in the Hungarian transmission network. The algorithm employs mixed-integer linear programming implemented using Python and MATLAB to achieve comprehensive network observability with minimal PMU deployment. The Hungarian network graph was constructed from data provided in the Union for the Coordination of Transmission of Electricity (UCTE) data exchange format, and the placement algorithm was applied. The results indicate that full network observability can be achieved by placing the PMUs at approximately one-third of the buses. Furthermore, the algorithm provides a strategic sequence for PMU placement, ensuring maximum information capture with each additional PMU while prioritizing critical buses such as those connected to major power plants and cross-border transmission lines. This method is scalable and can be adapted for any power network provided in the UCTE data exchange format.
引用
收藏
页数:4
相关论文
共 50 条
  • [1] the Method of Optimal Phasor Measurement Unit Placement
    Zhang Wen-jun
    Xu Jian-jun
    Xing Long
    ADVANCES IN APPLIED SCIENCE AND INDUSTRIAL TECHNOLOGY, PTS 1 AND 2, 2013, 798-799 : 298 - +
  • [2] Optimal Phasor Measurement Unit Placement by an Improved PSO Algorithm
    Wang, Jian-ming
    Li Chuandong
    Zhang, Jian
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [3] Optimal Placement of Phasor Measurement Unit for System Observability (Case Study: Southern Region Power System Network, Ethiopia)
    Negash, Kinfe
    Khan, Baseem
    Tesfaye, Damot
    Gayathri, M.
    2017 INTERNATIONAL CONFERENCE ON COMPUTING METHODOLOGIES AND COMMUNICATION (ICCMC), 2017, : 73 - 77
  • [4] Optimal Placement of Phasor Measurement Unit for Observation Reliability Enhancement
    Van-Khoi Tran
    Zhang, He-sheng
    Van-Nghia Nguyen
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2017, 12 (03) : 996 - 1006
  • [5] An Approach for Optimal Placement of Phasor Measurement Unit for Power Network Observability Considering Various Contingencies
    Rohit Babu
    Biplab Bhattacharyya
    Iranian Journal of Science and Technology, Transactions of Electrical Engineering, 2018, 42 : 161 - 183
  • [6] An Approach for Optimal Placement of Phasor Measurement Unit for Power Network Observability Considering Various Contingencies
    Babu, Rohit
    Bhattacharyya, Biplab
    IRANIAN JOURNAL OF SCIENCE AND TECHNOLOGY-TRANSACTIONS OF ELECTRICAL ENGINEERING, 2018, 42 (02) : 161 - 183
  • [7] PSO Based Optimal Phasor Measurement Unit Placement Considering Measurement Redundancy
    Subbaiyan, Thangavel
    Venkatachalam, Yuvaraju
    2020 3RD INTERNATIONAL CONFERENCE ON ENERGY, POWER AND ENVIRONMENT: TOWARDS CLEAN ENERGY TECHNOLOGIES (ICEPE 2020), 2021,
  • [8] Optimal Placement of Phasor Measurement Unit based on Bus Observation Reliability
    Tran, Van-Khoi
    Zhang, He-Sheng
    RECENT ADVANCES IN ELECTRICAL & ELECTRONIC ENGINEERING, 2019, 12 (01) : 68 - 78
  • [9] A Bounded Exhaustive Search Technique for Optimal Phasor Measurement Unit Placement in Power Grids
    Ibrahim, Ahmad Asrul
    Khalid, Khairuddin
    Shareef, Hussain
    Kamari, Nor Azwan Mohamed
    SYMMETRY-BASEL, 2020, 12 (12): : 1 - 13
  • [10] Islanding Based Optimal Placement of Phasor Measurement Unit using MILP
    Singh, Satyendra Pratap
    Singh, S. P.
    2016 IEEE 7TH POWER INDIA INTERNATIONAL CONFERENCE (PIICON), 2016,