Influence of Induction Machine Loads on Islanding Detection by Inverter-Based Distributed Generation

被引:0
作者
Kondoh, Junji [1 ]
机构
[1] Tokyo Univ Sci, Chiba 2788510, Japan
关键词
Induction machines; Reactive power; Islanding; Certification; Standards; Motors; Capacitors; Frequency; induction machine; islanding detection; moment of inertia; power conditioning subsystem; reactive power;
D O I
10.1109/TPWRD.2024.3452775
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An inverter-based distributed generation system with an interface unit called power conditioning subsystem (PCS) is required to prevent unintentional islanding immediately. Although the run-on time increases in a local isolated grid that includes an induction machine, the mechanism has not been clarified. In this study, first, an anti-islanding test system used for the PCS certification test in Japan was set up, and it was found that most of the reactive power provided by the PCS to promote frequency deviations was absorbed by the connected induction machine. Second, a modified equivalent circuit of a three-phase induction machine was proposed to simulate their behaviors numerically. The simulation results showed good agreement with the experimental results. Especially, the transient absorption of negative reactive power by the induction machine was accurately reproduced. Third, to investigate the mechanism behind the prolongation of the run-on time, the influence of the inertia of the induction machine was analyzed. It was found that there are worst values of moment of inertia that cause the least frequency fluctuation and the longest run-on time under respective islanding conditions. The results of this study contribute to a better understanding of the behavior and influence of induction machines under an islanding condition.
引用
收藏
页码:2985 / 2996
页数:12
相关论文
共 35 条
  • [1] Anayama T., 1955, Reports of the Faculty of Engineering, Yamanashi University., V6
  • [2] [Anonymous], 2018, IEEE Standard for Interconnection and Interoperability of DIstributed Energy Resources with Associated Electric Power Systems Interfaces
  • [3] Belloni F, 2013, 2013 48TH INTERNATIONAL UNIVERSITIES' POWER ENGINEERING CONFERENCE (UPEC)
  • [4] Bower W., 2002, Evaluation of islanding detection methods for utility-interactive inverters in photovoltaic systems
  • [5] Assessment of Unintentional Islanding Operations in Distribution Networks with Large Induction Motors
    Casals-Torrens, Pau
    Martinez-Velasco, Juan A.
    Serrano-Fontova, Alexandre
    Bosch, Ricard
    [J]. ENERGIES, 2020, 13 (02)
  • [6] Cooperative Study Group on Generic Model Development for Power Electronics System Simulations, 2016, IEEJ Technical Report, No. 1382.
  • [7] Ellis A, 2013, IEEE PHOT SPEC CONF, P3134, DOI 10.1109/PVSC.2013.6745122
  • [8] Automatic phase-shift method for islanding detection of grid-connected photovoltaic inverters
    Hung, GK
    Chang, CC
    Chen, CL
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2003, 18 (01) : 169 - 173
  • [9] Igarashi H., 2008, P 33 IEEE PHOT SPEC, P1
  • [10] Igarashi H, 2006, WORL CON PHOTOVOLT E, P2415