Flow distribution characteristics of gravity- and pump-driven CO2 two-phase thermosyphon loops with three evaporators

被引:1
作者
Tong, Zhen [1 ,2 ]
Wang, Peng [1 ,2 ]
Han, Zekun [1 ,2 ]
Wang, Wencheng [1 ,2 ]
机构
[1] Qingdao Univ Technol, Sch Environm & Municipal Engn, Qingdao 266520, Peoples R China
[2] Shandong Engn Res Ctr Hlth Environm & Low Carbon E, Qingdao 266520, Peoples R China
关键词
Multi-evaporator thermosyphon loop; Operating characteristic; Flow distribution; Liquid pump; CO2;
D O I
10.1016/j.ijrefrig.2025.02.011
中图分类号
O414.1 [热力学];
学科分类号
摘要
Currently, most two-phase thermosyphon loop (TPTL) systems used in data centers feature a multi-evaporator design. The flow rate of the working fluid through each evaporator is one of the crucial factors affecting the cooling effect of the TPTL. Therefore, this paper conducts a comparative study on the flow distribution patterns of gravity- and pump-driven multi-evaporator TPTLs. The impacts of flow resistance and load distribution on each branch's flow distribution of working fluid are analyzed. It was found that the flow distributions of both gravity- and pump-driven TPTLs were influenced by load distribution. Under non-uniform load conditions, the flow rate tended to skew towards evaporators with higher loads. Additionally, the flow distribution of the gravity-driven TPTL was highly affected by individual branch flow resistance, which was markedly different from the pump-driven TPTL. Under uniform load conditions, the flow rate of the pump-driven TPTL was generally evenly distributed among the evaporators.
引用
收藏
页码:76 / 87
页数:12
相关论文
共 24 条
[11]   Experimental study on the effect of fill ratio on an R744 two-phase thermosyphon loop [J].
Tong, Zhen ;
Liu, Xiao-Hua ;
Li, Zhen ;
Jiang, Yi .
APPLIED THERMAL ENGINEERING, 2016, 99 :302-312
[12]   An experimental investigation of an R744 two-phase thermosyphon loop used to cool a data center [J].
Tong, Zhen ;
Ding, Tao ;
Li, Zhen ;
Liu, Xiao-Hua .
APPLIED THERMAL ENGINEERING, 2015, 90 :362-365
[13]   Experimental assessment and numerical study of a pump-assisted loop heat pipe for high capacity thermal systems [J].
Vasta, Salvatore ;
Palomba, Valeria ;
La Rosa, Davide ;
Bonanno, Antonino .
APPLIED THERMAL ENGINEERING, 2020, 180
[14]   Experimental investigation on a loop thermosyphon with three evaporators: Unique startup and oscillation phenomena [J].
Zhang, Hainan ;
Shao, Shuangquan ;
Xu, Hongbo ;
Tian, Changqing .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 99 :363-370
[15]   The transient response, oscillation and internal flow of a loop thermosyphon with dual evaporators [J].
Zhang, Hainan ;
Shao, Shuangquan ;
Gao, Yuping ;
Xu, Hongbo ;
Tian, Changqing .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 88 :451-457
[16]   The effect of heating power distribution on the startup time and overshoot of a loop thermosyphon [J].
Zhang, Hainan ;
Shao, Shuangquan ;
Gao, Yuping ;
Xu, Hongbo ;
Tian, Changqing .
APPLIED THERMAL ENGINEERING, 2018, 132 :554-559
[17]  
Zhang Hainan, 2021, J. Case Stud. Thermal Eng., V28
[18]   Experimental research on dynamic characteristics and control strategy of the pump-driven two-phase loop with dual evaporators [J].
Zhang, Penglei ;
Liu, Kehan ;
Li, Yue ;
Yang, Xiaorui ;
Li, Xiaolin .
CASE STUDIES IN THERMAL ENGINEERING, 2022, 38
[19]   Comparative study of two-phase natural circulation and gas-side mechanically driven loop used in air-conditioning systems [J].
Zhang, Penglei ;
Li, Xianting ;
Li, Rongjia ;
Shi, Wenxing ;
Wang, Baolong .
APPLIED THERMAL ENGINEERING, 2019, 153 :848-860
[20]   Experimentally comparative study on two-phase natural and pump-driven loop used in HVAC systems [J].
Zhang, Penglei ;
Li, Xianting ;
Shi, Wenxing ;
Wang, Baolong ;
Rong, Xingyue .
APPLIED THERMAL ENGINEERING, 2018, 142 :321-333