Partial Discharge and Motion Characteristics of Linear Metal Particles in SF6 Under AC Superimposed Lightning Impulse Voltage

被引:0
作者
Han, Xutao [1 ]
Wu, Xutao [2 ]
Zhao, Yingying [3 ]
Niu, Bo [2 ]
Wang, Haotian [1 ]
Li, Junhao [1 ]
机构
[1] State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, Xi’an
[2] Electric Power Science Research Institute, State Grid Ningxia Electric Power Co., Ltd., Yinchuan
[3] State Grid Shanghai Electric Power Co., Shanghai
来源
Gaodianya Jishu/High Voltage Engineering | 2024年 / 50卷 / 12期
关键词
AC superimposed lightning impulse; gas insulated switchgear; linear metal particles; motion characteristics; partial discharge;
D O I
10.13336/j.1003-6520.hve.20232109
中图分类号
学科分类号
摘要
GIS equipment often suffers from lightning overvoltage during operation, and the equipment actually bears the effect of AC superimposed lightning impulse voltage. At this time, high amplitude impulse voltage excites linear metal particles to start moving and generate partial discharge, seriously threatening the safe operation of GIS equipment. Therefore, this paper establishes an AC superimposed lightning impulse voltage test system, which combines partial discharge measurement and optical image observation methods to study the partial discharge characteristics and motion behavior of linear metal particles in SF6 gas under AC superimposed lightning impulse voltage. Combined the the partial discharge characteristics and motion behavior of linear metal particles, the motion mechanism and partial discharge mechanism of linear metal particles under AC superimposed lightning impulse voltage are analyzed. The results show that the superimposed voltage can stimulate the movement of linear metal particles; however, after the action of lightning impulse voltage, there is no obvious partial discharge signal immediately. Instead, a continuous partial discharge begins to occur after a delay time, which is related to the physical size and number of the defect. In addition, jumping motion through the electrode is more likely to occur during the subsequent continuous discharge process. The research work in this paper is conducive to a deeper understanding of the motion characteristics of metal particles in actual equipment and the process of causing partial discharge, and has guiding significance for equipment operation and maintenance analysis and equipment manufacturing improvement. © 2024 Science Press. All rights reserved.
引用
收藏
页码:5406 / 5414
页数:8
相关论文
共 23 条
[1]  
LI Xiaoang, LI Jie, REN Jing, Et al., Lift-off characteristics of free metal particles in GIS under shock vibration, High Voltage Engineering, 48, 5, pp. 2005-2012, (2022)
[2]  
LI Qingmin, WANG Jian, LI Botao, Et al., Review on metal particle contamination in GIS/GIL, High Voltage Engineering, 42, 3, pp. 849-860, (2016)
[3]  
LI Xing, XU Yaun, DING Dengwei, LIU Weidong, Influence of temperature on partial discharge and flashover characteristics of metal particle on GIS insulator surface, Proceedings of the CSEE, 42, 1, pp. 406-414, (2022)
[4]  
LI Qingmin, WEI Lai, XUE Naifan, Et al., Research advances in visualization detection technology of micron-nano dust in AC and DC GIS/GIL, High Voltage Engineering, 49, 9, pp. 3607-3624, (2023)
[5]  
COOKSON A H, FARISH O, SOMMERMAN G M L., Effect of conducting particles on AC corona and breakdown in compressed SF6, IEEE Transactions on Power Apparatus and Systems, PAS-91, 4, pp. 1329-1338, (1972)
[6]  
ZHANG Guangdong, NIU Xuesong, WANG Xiaofei, Et al., Partial discharge detection and characteristics probe of free metal particles in GIS based on UHF method, Industrial Instrumentation & Automation, 1, pp. 101-105, (2015)
[7]  
YIN Hua, HU Panfeng, ZHANG Xiaoyong, Et al., The application of UHF detection to partial discharge in GIS caused by fixed metal particle, High Voltage Apparatus, 40, 6, pp. 409-411, (2004)
[8]  
SHI Wen, YANG Zhengli, CHEN Haixia, Et al., Characteristic analysis of partial discharge signals of free metal particle defects in GIS, High Voltage Apparatus, 56, 11, pp. 139-144, (2020)
[9]  
WU Zhicheng, ZHANG Qiaogen, SONG Jiajie, Et al., Phase resolved partial discharge pattern of free conductive particle defects in GIS, High Voltage Engineering, 45, 6, pp. 1995-2002, (2019)
[10]  
MORCOS M M, ZHANG S, SRIVASTAVA K D, Et al., Dynamics of metallic particle contaminants in GIS with dielectric-coated electrodes, IEEE Transactions on Power Delivery, 15, 2, pp. 455-460, (2000)