EXPERIMENTAL AND SIMULATION STUDY ON TRANSCRITICAL CO2 AIR SOURCE HEAT PUMP WATER HEATER

被引:0
作者
Yang, Junlan [1 ]
Chen, Dandan [1 ]
Zhang, Xin [1 ]
机构
[1] School of Energy and Security Engineering, Tianjin Chengjian University, Tianjin
来源
Taiyangneng Xuebao/Acta Energiae Solaris Sinica | 2024年 / 45卷 / 12期
关键词
air source heat pump; CO[!sub]2[!/sub; ejector; quasi-two-stage; system performance;
D O I
10.19912/j.0254-0096.tynxb.2023-1191
中图分类号
学科分类号
摘要
In order to improve the performance of CO2 air source heat pump water heater,an experimental device was built,and the effects of cooling water flow,high pressure and compressor frequency were tested. Furthermore,the simulation model of trans-critical CO2 quasi-two-stage compression heat pump with ejector(TCIEJ) was established,and the system performance was simulated. The results show that when the flow rate of cooling water increases from 70 kg/h to 122.5 kg/h,COP increases by 30%,while the outlet temperature of cooling water decreases by 15.4%. With the increase of high pressure,the COP has a maximum value,the outlet temperature of gas cooler and cooling water both increase. When the compressor frequency increases from 110 Hz to 180 Hz,the exhaust pressure increases by 22.3%,but COP decreases by 44.6%. When the high pressure of TCIEJ system increases from 8.0 MPa to 10.4 MPa,the outlet temperature of cooling water increases by 17.66 ℃,even when the ambient temperature is 0 ℃ and the high pressure reaches 10.4 MPa,the exhaust temperature of the compressor is only 85.77 ℃,this system is conducive to improving the compression process. When the flow rate of cooling water increases from 60 L/h to 100 L/h,the outlet temperature of cooling water decreases by 6.8 ℃. © 2024 Science Press. All rights reserved.
引用
收藏
页码:581 / 587
页数:6
相关论文
共 15 条
  • [1] GONG G C,, LI B L, ZHOU F Y,, Et al., Research on simulation model of distributed parameter air source heat pump based on PID-bisection combination control algorithm[J], Acta energiae solaris sinica, 43, 7, pp. 16-21, (2022)
  • [2] LI H, ZHANG C L., Developments and application analysis of carbon dioxide heat pump[J], Chemical industry and engineering progress, 35, pp. 421-426, (2016)
  • [3] WANG J,, BELUSKO M,, EVANS M,, Et al., A comprehensive review and analysis on CO<sub>2</sub> heat pump water heaters[J], Energy conversion and management, 15, (2022)
  • [4] CHEN Z D, LUO H L, DU P J,, Et al., Research of variable frequency performance of CO<sub>2</sub> air source heat pump on heating[J], Acta energiae solaris sinica, 41, 3, pp. 219-225, (2020)
  • [5] ZHANG Z G, LIU Y, YAO W X., Energy efficyency analysys of air energy water heater in cold area in winter [J], Acta energiae solaris sinica, 44, 1, pp. 543-550, (2023)
  • [6] WANG X L,, Et al., Experimental investigation of the optimal heat rejection pressure for a transcritical CO<sub>2</sub> heat pump water heater[J], Applied thermal engineering, 56, 1-2, pp. 120-125, (2013)
  • [7] YE Z L, CAO F., Experimental study and optimal control strategy of a transcritical CO<sub>2</sub> heat pump water heater[J], IOP conference series:materials science and engineering, 604, 1, (2019)
  • [8] LIU X F, ZHANG Z,, Et al., Experimental study on the performance of water source trans-critical CO<sub>2</sub> heat pump water heater [J], Energies, 10, 6, (2017)
  • [9] YANG J L, WU Y T,, WANG C X, Et al., Experimental study on transcritical CO<sub>2</sub> water to water heat pump system [J], Cryogenics & superconductivity, 48, 4, pp. 79-84, (2020)
  • [10] YANG L X., Experimental study on characteristics of transcritical CO<sub>2</sub> heat pump system and influencing factors of outlet water temperature[D], (2019)