Security Region-Based Probabilistic Stability Analysis of Sub/Super-Synchronous Oscillation in Wind Power Integrated Power Systems

被引:0
|
作者
Zhan, Ying [1 ]
Xie, Xiaorong [2 ]
Zhang, Xu [1 ]
机构
[1] China Univ Min & Technol Beijing, Sch Mech & Elect Engn, Beijing 100083, Peoples R China
[2] Tsinghua Univ, Dept Elect Engn, State Key Lab Power Syst Operat & Control, Beijing 100084, Peoples R China
来源
IEEE ACCESS | 2024年 / 12卷
基金
中国国家自然科学基金; 中国博士后科学基金;
关键词
Power system stability; Oscillators; Stability criteria; Probabilistic logic; Wind power generation; Security; Damping; Accuracy; Wind speed; Indexes; Security region; probabilistic stability analysis; sub/super-synchronous oscillation; wind power integrated power system; SMALL-SIGNAL STABILITY; FARMS; PENETRATION; DFIG;
D O I
10.1109/ACCESS.2024.3488097
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The stability of sub/super- synchronous oscillation (SSO) is dependent on system operating conditions. However, the existing stability analysis methods mostly investigate the SSO stability under a specific condition, which cannot reflect the real SSO risk. To address the issue, this paper proposes a security region (SR)-based probabilistic stability analysis method. Firstly, an efficient high-dimensional SR construction method is proposed based on the predictor-corrector technique. And several hyperplanes are adopted to fit the SR boundary. Then based on the SR, the probabilistic stability coefficient and stability margin index is established, so that the SSO risk under uncertain operating conditions can be evaluated and the dominant oscillation mode as well as sensitive nodes can be identified. This will provide significance guidance on the planning and operation of the system. Finally, the proposed method is conducted on a practical wind power system. The influence of the number of WTGs, wind speed distribution parameters as well as correlation on SSO probabilistic stability is studied. Compared with the traditional Monte-Carlo simulation method, the computational efficiency is improved by over 20 times. Thus verifies the effectiveness of the proposed method.
引用
收藏
页码:160776 / 160783
页数:8
相关论文
共 50 条
  • [21] Observability and Controllability Analysis of Sub-/Super-synchronous Components Based on Frequency Domain Oscillation Mode
    Ren J.
    Xiao S.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2023, 47 (03): : 30 - 39
  • [22] Application of Sub/super-synchronous Power for Identifying the Source of Subsynchronous Control Interaction
    Ma, Yue
    Huang, Qi
    Cai, Dongsheng
    Zhang, Zhenyuan
    2021 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2021,
  • [23] Research on sub/super-synchronous oscillation suppression method for direct-drive wind turbine based on energy compensation
    Ma, Jing
    Zhang, Min
    Phadke, A. G.
    IET RENEWABLE POWER GENERATION, 2021, 15 (11) : 2502 - 2514
  • [24] A probabilistic security assessment approach to power systems with integrated wind resources
    Le, D. D.
    Berizzi, A.
    Bovo, C.
    RENEWABLE ENERGY, 2016, 85 : 114 - 123
  • [25] Active Control Strategy for Wind Farm Systems to Prevent Sub/super-Synchronous Oscillations
    Wang, Haijiao
    Liu, Chun
    2021 3RD ASIA ENERGY AND ELECTRICAL ENGINEERING SYMPOSIUM (AEEES 2021), 2021, : 385 - 390
  • [26] Wind-farm-level sub-/super-synchronous oscillation suppression strategy based on generalized reactance sensitivity
    Shen, Ruixin
    Duan, Tao
    Zhang, Xian
    Liu, Weipeng
    Dong, Shengxi
    ENERGY REPORTS, 2023, 9 : 558 - 569
  • [27] Wind-farm-level sub-/super-synchronous oscillation suppression strategy based on generalized reactance sensitivity
    Shen, Ruixin
    Duan, Tao
    Zhang, Xian
    Liu, Weipeng
    Dong, Shengxi
    ENERGY REPORTS, 2023, 9 : 558 - 569
  • [28] Sub and super-synchronous wind turbine-doubly fed induction generator system implemented as an active power filter
    Djeghloud H.
    Bentounsi A.
    Benalla H.
    International Journal of Power Electronics, 2011, 3 (02) : 189 - 212
  • [29] Location of Sub-/Super-synchronous Oscillation Source for Direct-driven Wind Turbines Based on Deep Subdomain Adaptation
    Hao Q.
    Liu C.
    Wang J.
    Wang X.
    Su C.
    Zheng L.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2023, 47 (17): : 27 - 37
  • [30] Sub Synchronous Oscillation in Asynchronous Generators Serving to Wind and Hydro Power Systems - A Review
    Mohale, Vijay
    Chelliah, Thanga Raj
    2021 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING (IAS), 2021,