Molecular Simulation Study on the Adsorption Mechanisms of Microbial Components and Metabolic Products on Activated Carbon in HVAC Systems

被引:0
作者
Zhang, Ge [1 ]
Peng, Zhiyuan [1 ]
Liu, Shuai [1 ]
Li, Xiaochen [1 ]
机构
[1] School of Civil and Resource Engineering, University of Science and Technology Beijing, Beijing
关键词
activated carbon; molecular simulation; p-xylene; peptidoglycan;
D O I
10.3390/pr12122763
中图分类号
学科分类号
摘要
Activated carbon is widely known for its porous structure and diverse surface functional groups, making it an effective adsorbent for removing various organic and inorganic pollutants from air and water. However, as a filtration material in air conditioning systems, activated carbon can also provide favorable conditions for microbial growth, potentially leading to the proliferation of microorganisms on its surface. These microorganisms, along with their metabolic products, can be released into indoor environments, posing potential health risks. This study employs molecular simulation to investigate the adsorption and release mechanisms of microorganisms and their volatile organic compound (VOC) metabolic products on activated carbon. Peptidoglycan (PDG) (as a representative bacterial cell wall component) and p-xylene (as a representative microbial metabolic product) were used as model compounds. The adsorption behavior of these compounds was simulated on activated carbon under different environmental conditions, including varying temperatures. The study found that activated carbon has a higher affinity for peptidoglycan than for p-xylene; at 303.15 K, the diffusion coefficients of peptidoglycan and p-xylene in activated carbon are 0.842 × 10−9 m2/s and 0.587 × 10−8 m2/s, respectively. Temperature plays an important role in affecting adsorption capacity; when the temperature rises by 10 K, the diffusion coefficients of peptidoglycan and p-xylene in activated carbon increase by 32.8% and 34.3%, respectively. These insights contribute to the development of efficient and health-conscious air purification materials, offering theoretical and practical guidance for optimizing the use of activated carbon in HVAC systems. © 2024 by the authors.
引用
收藏
相关论文
共 52 条
  • [1] Kumari M., Chaudhary G.R., Chaudhary S., Umar A., Transformation of solid plastic waste to activated carbon fibres for wastewater treatment, Chemosphere, 294, (2022)
  • [2] Zhao X., Qi F., Li H., Shi Z., The activation of carbon materials to control airborne pathogenic bacteria in the pig house by efficient adsorption, Biosyst. Eng, 236, pp. 71-78, (2023)
  • [3] Al-Fawzan F.F., An Eco-Friendly Procedure for Preparation of Activated Carbon as a Capture Material of Heavy Metals in Wastewater, Sci. Adv. Mater, 12, pp. 1157-1163, (2020)
  • [4] Liu Z., Ma S., Cao G., Chong M., Bao-Jie H., Distribution characteristics, growth, reproduction and transmission modes and control strategies for microbial contamination in HVAC systems: A literature review, Energy Build, 177, pp. 77-95, (2018)
  • [5] Liu Z., Cheng K., Li H., Cao G., Wu D., Shi Y., Exploring the potential relationship between indoor air quality and the concentration of airborne culturable fungi: A combined experimental and neural network modeling study, Environ. Sci. Pollut. Res, 25, pp. 3510-3517, (2018)
  • [6] Nevalainen A., Taubel M., Hyvarinen A., Indoor fungi: Companions and contaminants, Indoor Air, 25, pp. 125-156, (2015)
  • [7] Forthomme A., Joubert A., Andres Y., Simon X., Duquenne P., Bemer D., Le Coq L., Microbial aerosol filtration: Growth and release of a bacteria–fungi consortium collected by fibrous filters in different operating conditions, J. Aerosol Sci, 72, pp. 32-46, (2014)
  • [8] Lv Y., Hu G., Wang C., Yuan W., Wei S., Gao J., Wang B., Song F., Actual measurement, hygrothermal response experiment and growth prediction analysis of microbial contamination of central air conditioning system in Dalian, China, Sci. Rep, 7, (2017)
  • [9] Haines S.R., Hall E.C., Marciniak K., Misztal P.K., Goldstein A.H., Adams R.I., Dannemiller K.C., Microbial growth and volatile organic compound (VOC) emissions from carpet and drywall under elevated relative humidity conditions, Microbiome, 9, (2021)
  • [10] Danko D., Bezdan D., Afshin E.E., Ahsanuddin S., Bhattacharya C., Butler D.J., Chng K.R., Donnellan D., Hecht J., Jackson K., Et al., A global metagenomic map of urban microbiomes and antimicrobial resistance, Cell, 184, (2021)