Modulation strategy of dynamic voltage restorer based on dual-feedforward active disturbance rejection compound controller

被引:0
作者
Huang, Langchen [1 ]
Liu, Weiling [1 ]
Zhang, Ning [1 ]
Yan, Qingyun [1 ]
Wei, Xinwei [2 ]
机构
[1] College of Electrical and Information Engineering, Hunan University of Technology, Zhuzhou
[2] College of Electrical and Power Engineering, Taiyuan University of Technology, Taiyuan
关键词
active disturbance rejection controller; distribution network; dynamic voltage restorer; feedforward compensation; power quality management; voltage sag;
D O I
10.3389/fenrg.2024.1462565
中图分类号
学科分类号
摘要
Given the contradiction between compensating speed and compensating overshoot in traditional Proportional Integral (PI) control of Dynamic Voltage Restorer (DVR), A Feedforward compensation-active Disturbance Rejection Control (FC-ADRC) strategy based on Feedforward Compensation is proposed. ADRC control is used to improve the problem of compensating oversets existing in traditional PI control, and the voltage and current of the LC filter are introduced as the feedforward quantity to compensate the DVR controller to realize the rapid voltage compensation for the voltage dip on the user side and ensure the safety and stability of the voltage on the user side. The simulation results show that the proposed control strategy not only keeps the high dynamic response of the DVR device but also ensures the device’s adaptability to deal with uncertain disturbances. Copyright © 2025 Huang, Liu, Zhang, Yan and Wei.
引用
收藏
相关论文
共 26 条
[1]  
Appala T.N., Raj S.A., Rakesh M., Sanjeevikumar P., Variable fractional power-least mean square based control algorithm with optimized PI gains for the operation of dynamic voltage restorer, IET Power Electron, 14, 4, pp. 821-833, (2021)
[2]  
Arya S.R., Mistry K.D., Kumar P., DVR using randomized self-structuring fuzzy and recurrent probabilistic fuzzy neural-based controller, J. Institution Eng. (India) Ser. B, 105, 3, pp. 483-502, (2024)
[3]  
Ben-run H., Li X., Zheng-Guo W., Wei-Ping Z., Application of active disturbance rejection controller in dynamic voltage restorer, Electr. Mach. Control, 16, 6, pp. 106-110, (2012)
[4]  
Chen Z., Song M., Liu S., Factors influencing the test results of voltage sag immunity, Med. Equip, 35, 21, pp. 37-39, (2022)
[5]  
Deshpande C.V., Chilipi R., Arya S.R., Modified fractional least mean square-based control scheme for dynamic voltage restorer to improve power quality, Electr. Eng, 106, 4, pp. 5069-5087, (2024)
[6]  
Gao Z., Inheritance and development of active disturbance rejection control, Control Theory Appl, 40, 3, pp. 593-595, (2023)
[7]  
Gu Y., Cheng-Jian L., Yao X., Fang J.L., Sheng H., Research and application of Power Supply service effectiveness Improvement based on Power quality fine control, Electr. Appliances Energy Effic. Manag. Technol, 593, 8, pp. 94-99, (2020)
[8]  
Guan W., Qinglei1 Z., Siyuan Z., Kaiwen H., Boyu Q., Zhengchun D., Research on Evaluation System of grid structure considering load loss, New Technol. Electroengineering Electr. Energy, 42, 1, pp. 40-47, (2023)
[9]  
Hong C., Zhun Y., Overview of power quality analysis, China Insp. Test, 30, 5, pp. 11-14, (2022)
[10]  
Huiyu J., Song J., Lan W., Gao Z., On the characteristics of ADRC: a PID interpretation, Sci. China Infor- mation Sci, 63, 10, pp. 258-260, (2020)