Inverter-Embedded DFIG Rotor Winding Insulation Testing for Wind Energy Applications

被引:0
作者
Park, Cheol-Hui [1 ]
Zapico, Marcos Orviz [2 ]
Bolanos, Adrian Salcedo [3 ]
Reigosa, David Diaz [2 ]
Byun, Namhyuk [3 ]
del Blanco, Fernando Briz [3 ]
Osama, Mohamed [4 ]
Lee, Sang Bin [3 ]
机构
[1] Samsung Elect, Suwon 16677, South Korea
[2] Univ Oviedo, Dept Elect Comp & Syst Engn, Gijon 33204, Spain
[3] Korea Univ, Dept Elect Engn, Seoul 02841, South Korea
[4] GE Aviat, D-85748 Munich, Germany
基金
新加坡国家研究基金会;
关键词
Insulation; Rotors; Doubly fed induction generators; Testing; Stress; Windings; Voltage measurement; Capacitance (C); dissipation factor (DF); doubly -fed induction generator (DFIG); fault diagnosis; insulation testing; inverter; off-line testing; partial discharge (PD); FED INDUCTION GENERATOR; MACHINES; FAULTS; VOLTAGE;
D O I
10.1109/TIA.2024.3443788
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Failure in the rotor winding insulation of doubly-fed induction generators (DFIG) is common due to the harsh environment and operating stresses. However, testing rotor insulation is difficult and costly due to the limited accessibility of wind generators as they are installed at remote locations inside the nacelle. Therefore, remote and automated insulation testing can help improve the reliability and reduce maintenance cost of wind generators. In this paper, a new approach for testing the integrity of rotor winding insulation for DFIGs is proposed. The main idea is to use the rotor-side inverter to perform off-line insulation testing whenever the wind generator is stopped. New test methods for off-line 1) partial discharge (PD) detection based on impulse voltage excitation and 2) capacitance (C) and dissipation factor (DF) testing based on common mode voltage excitation are proposed. Testing on a 6.3 kW wound rotor induction machine is given to verify the effectiveness of the proposed rotor insulation test method.
引用
收藏
页码:9195 / 9205
页数:11
相关论文
共 26 条
[21]   Evaluation of the Control Limit of Rotor-Side Converters in DFIG-based Wind Energy Conversion Systems under Symmetrical Voltage Dips [J].
Zhou, Honglin ;
Yang, Geng ;
Geng, Hua .
2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
[22]   Performance evaluation of an optimized simplified nonlinear active disturbance rejection controller for rotor current control of DFIG-based wind energy system [J].
Sobhy, Ahmed ;
Elfar, Medhat Hegazy ;
Refaat, Ahmed ;
Fawzi, Mahmoud .
CLEANER ENGINEERING AND TECHNOLOGY, 2025, 24
[23]   Control of a DFIG-based wind energy conversion system operating under harmonically distorted unbalanced grid voltage along with nonsinusoidal rotor injection conditions [J].
Fathabadi, Hassan .
ENERGY CONVERSION AND MANAGEMENT, 2014, 84 :60-72
[24]   Quasi-steady-state rotor EMF-oriented vector control of doubly fed winding induction generators for wind-energy generation [J].
Huang, Hui ;
Fan, Yu ;
Qiu, Rui-Chang ;
Jiang, Xue-Dong .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2006, 34 (11) :1201-1211
[25]   A New Nonlinear Virtual Inertia Approach to Mitigate Destructive Effects of Cyber Attacks on Active Power and Rotor Speed Profiles of Wind Turbine DFIG Sustainable Energy Production [J].
Mahvash, Hossein ;
Taher, Seyed Abbas ;
Guerrero, Josep M. .
SMART GRIDS AND SUSTAINABLE ENERGY, 2024, 9 (01)
[26]   Grid-forming assisted based power management of AC microgrid system comprising multiple battery energy storage units, DFIG-based wind turbines and inverter-based resources [J].
Ghadiriyan, Sajjad ;
Rahimi, Mohsen .
JOURNAL OF ENERGY STORAGE, 2024, 97