Study on Transformer Online Discrimination Using Light Transmittance of Insulating Oil

被引:0
|
作者
Moon, Seungpil [1 ]
Bang, Hyeongpil [1 ]
Choi, Jang-Heum [1 ]
Lee, Yeonchan [1 ]
机构
[1] KEPCO Research Institute, Korea, Republic of
关键词
Fault Discrimination; insulating oil; light transmittance; Transformer;
D O I
10.5370/KIEE.2024.73.11.1910
中图分类号
学科分类号
摘要
The purpose of this study is the fault discrimination of the transformer that supplies power in demand. In this study, the correlation between the light transmittance of the insulating oil and dielectric breakdown was used to the fault discrimination of the transformer. In this study, the light sources of various wavelengths were compared, and it was shown in the paper that the selected 520 nm light sources can clearly diagnose the deterioration state. In addition, in order to evaluate the total dielectric breakdown of the insulating oil, research was conducted through various samples through the collection of insulating oil samples and acceleration deterioration tests of the used transformer. It is believed that the diagnostic method for the state of the transformer using the light transmittance of the insulating oil proposed through this study can help secure the reliability and economy of the power facility. Copyright © The Korean Institute of Electrical Engineers.
引用
收藏
页码:1910 / 1916
页数:6
相关论文
共 50 条
  • [31] Method to Evaluate the Degradation Condition of Transformer Insulating Oil - Experimental Study on the Hydrophilic and Dissociative Properties of Degradation Products
    Wada, Junichi
    Ueta, Genyo
    Okabe, Shigemitsu
    Amimoto, Tsuyoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (02) : 873 - 881
  • [32] Study on the Improvement of Light Transmittance of Polyester Film
    Kim, Si-Min
    Park, Soo-Young
    POLYMER-KOREA, 2012, 36 (05) : 662 - 667
  • [33] Study on Influence of Oxidation on Static Electrification in Transformer Oil
    Shima, K.
    Tsuchie, M.
    Kozako, M.
    Hikita, M.
    Gosho, Y.
    PROCEEDINGS OF THE 2014 IEEE 18TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL 2014), 2014,
  • [34] Influence of electrical and thermal ageing on the mineral insulating oil performance for power transformer applications
    Ranga, C.
    Kumar, A.
    Chandel, R.
    INSIGHT, 2020, 62 (04) : 222 - 231
  • [35] Mixed Insulating Liquids With Mineral Oil for High-Voltage Transformer Applications: A Review
    Lyutikova, Marina N.
    Korobeynikov, Sergey M.
    Rao, U. Mohan
    Fofana, Issouf
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (02) : 454 - 461
  • [36] Influence of Trace Components Contained in Transformer Insulating Oil on Various Characteristics over Time
    Wada, Junichi
    Ueta, Genyo
    Okabe, Shigemitsu
    Amimoto, Tsuyoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (04) : 1388 - 1394
  • [37] Experimental Study of the Compatibility of Insulating Oil in Transformers
    Electric Power Research Institute of Guangdong Power Grid Corporation, Guangzhou, China
    不详
    Mater. Res. Innov., (680-684): : 680 - 684
  • [38] Inhibition Technique of Transformer Insulating Oil Degradation - Evaluation of the Effectiveness of Oxidation Degradation Inhibitors
    Wada, Junichi
    Ueta, Genyo
    Okabe, Shigemitsu
    Amimoto, Tsuyoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (05) : 1641 - 1648
  • [39] Transmittance Spectra of Oxidized Insulation Oil using Terahertz Spectroscopy
    Nishimura, Nobuaki
    Ogura, Ryuich
    Matsumoto, Satoshi
    Mizuno, Maya
    Fukunaga, Kaori
    2011 IEEE INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2011,
  • [40] New near-infrared absorbance peak for inhibitor content detection in transformer insulating oil
    Leong, Yang Sing
    Ker, Pin Jern
    Jamaludin, M. Z.
    Nomanbhay, Saifuddin M.
    Ismail, Aiman
    Abdullah, Fairuz
    Looe, Hui Mun
    Shukri, C. Nuru Saniyyati M.
    SENSORS AND ACTUATORS B-CHEMICAL, 2018, 266 : 577 - 582