Study on Transformer Online Discrimination Using Light Transmittance of Insulating Oil

被引:0
作者
Moon, Seungpil [1 ]
Bang, Hyeongpil [1 ]
Choi, Jang-Heum [1 ]
Lee, Yeonchan [1 ]
机构
[1] KEPCO Research Institute, Korea, Republic of
关键词
Fault Discrimination; insulating oil; light transmittance; Transformer;
D O I
10.5370/KIEE.2024.73.11.1910
中图分类号
学科分类号
摘要
The purpose of this study is the fault discrimination of the transformer that supplies power in demand. In this study, the correlation between the light transmittance of the insulating oil and dielectric breakdown was used to the fault discrimination of the transformer. In this study, the light sources of various wavelengths were compared, and it was shown in the paper that the selected 520 nm light sources can clearly diagnose the deterioration state. In addition, in order to evaluate the total dielectric breakdown of the insulating oil, research was conducted through various samples through the collection of insulating oil samples and acceleration deterioration tests of the used transformer. It is believed that the diagnostic method for the state of the transformer using the light transmittance of the insulating oil proposed through this study can help secure the reliability and economy of the power facility. Copyright © The Korean Institute of Electrical Engineers.
引用
收藏
页码:1910 / 1916
页数:6
相关论文
共 11 条
[1]  
Park Hyun-joo, Kim Suk-bun, Proposals for an Optimum Analysis Method for Furanic Compound in Insulating Oil for Paper Degradation Assessment, KIEE Summer Conference, (2009)
[2]  
Kim Choon-Dong, Kim Chol-Gyu, Park Sh-Hyun, Development of Portable Dissolved Gas Analyzer Using photoacoustic spectroscopy, Journal of the Korea Institute of Information and Communication Engineering, 17, 10, pp. 2431-2438, (2013)
[3]  
Kang Hyeong-Gu, Jang Jin-Young, Jang Seongguen, Kim Insu, A transformer lifetime prediction and failure diagnosis algorithm using probability theories, The 53rd KIEE Summer Conference, (2022)
[4]  
Im Haksun, Kim Beopsoo, Kim Insu, Study on Optimizing Transformer Replacement Cycle, The Korean Institute of Illumination and Electrical Installation Engineers, Proceedings of 2019 KIIEE Fall Annual Conference, (2019)
[5]  
Ryu Sangmin, Moon Seungpil, A Basic Study on the Status Diagnosis of Transformer Using Physical Properties of Insulating oil, KIEE Summer Conference, pp. 1720-1721, (2020)
[6]  
Moon Seungpil, Kang Shyung, Hwang Sun-jin, Choi SJongkee, Basic study on the method of utilizing the transmittance of insulation oil for diagnosing a transformer, KIEE Summer Conference, pp. 350-351, (2020)
[7]  
Hafez Al, Gerges NS, El-nagar KI, Mohamed SE, Heshem Al, Treatment of aged transformer oil using dry sludge in lab-scale refining unit, Journal of Oil, Gas and Coal Engineering, 2, 1, pp. 010-022, (2015)
[8]  
ISLAM Md Mominul, LEE Gareth, Nilendra HETTIWATTE Sujeewa, A review of condition monitoring techniques and diagnostic tests for lifetime estimation of power transformers, Electrical Engineering, 100, pp. 581-605, (2018)
[9]  
Duval Michel, Depablo Alfonso, Interpretation of Gas-In-Oil Analysis Using New IEC Publication 60599 and IEC TC 10 Database, IEEE Electrical Insulation Magazine, 17, 2, pp. 31-41, (2001)
[10]  
Duval Michel, The Duval Triangle for Load Tap Changers, Non-Mineral Oils and Low Temperature Faults in Transformer, IEEE Electrical Insulation Magazine, 24, 6, pp. 22-29, (2008)