Accurate Estimation of Transformer Winding Capacitances and Voltage Distribution Factor Using Driving Point Impedance Measurements

被引:2
作者
Samal, Manoj [1 ]
Prasanna, K. Lakshmi [1 ]
Mishra, Palash [2 ]
Mondal, Mithun [1 ]
机构
[1] Birla Inst Technol & Sci Pilani, Dept Elect & Elect Engn, Hyderabad, Telangana, India
[2] Natl Inst Technol Warangal, Dept Elect Engn, Warangal 506004, Telangana, India
关键词
Windings; Power transformer insulation; Voltage measurement; Estimation; Transformers; Accuracy; Capacitance measurement; Capacitance estimation; driving point impedance; ladder network; transformer diagnostics; transformer windings; voltage distribution factor; ESTIMATE SERIES CAPACITANCE; FREQUENCY-RESPONSE; AXIAL DISPLACEMENT; RADIAL DEFORMATION; FRA DIAGNOSTICS; LADDER NETWORK; LOCALIZATION; IDENTIFICATION; INDUCTANCE;
D O I
10.1109/ACCESS.2024.3460968
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper introduces an innovative methodology for precisely estimating winding capacitances (Cs and Cg) and the voltage distribution factor (alpha) in transformers using measured Driving Point Impedance (DPI) data. These parameters are critical for designing robust insulation systems and ensuring reliability during transient events. Unlike traditional approaches that rely on complex analytical models, impulse tests, or Finite Element Method (FEM) simulations, this method streamlines the estimation process by directly utilizing DPI measurements. Experimental validations across various winding configurations, including continuous and interleaved disc winding transformers, confirm the accuracy and versatility of this approach. The methodology presented offers substantial practical benefits for transformer condition monitoring. It facilitates efficient diagnostics of transformer deformations and impulse voltage distribution by estimating critical parameters from terminal measurements. The effect of noise on DPI data and the effectiveness of filtering techniques in enhancing parameter estimation accuracy have been rigorously analysed, demonstrating the method's reliability. This approach is especially useful for newly constructed transformers that need design validation or for older transformers with incomplete design records. It provides a practical, efficient, and straightforward diagnostic solution, proving valuable for both researchers and engineers.
引用
收藏
页码:133670 / 133684
页数:15
相关论文
共 48 条
[31]   Diagnosing Axial Displacement in an Actual, Single, Isolated Transformer Winding: Experimental Results [J].
Mukherjee, Pritam ;
Satish, L. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (02) :1280-1287
[32]   Localization of Radial Displacement in an Actual Isolated Transformer Winding-An Analytical Approach [J].
Mukherjee, Pritam ;
Satish, L. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (06) :2511-2519
[33]   Construction of Equivalent Circuit of a Single and Isolated Transformer Winding From FRA Data Using the ABC Algorithm [J].
Mukherjee, Pritam ;
Satish, L. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (02) :963-970
[34]   A comparison between partial discharge propagation in multiple-α and single-α transformer winding [J].
Naderi, MS ;
Vakilian, M ;
Blackburn, TR ;
Phung, BT ;
Zhang, H ;
O, HN ;
Naderi, MS .
PROCEEDINGS: ELECTRICAL INSULATION CONFERENCE AND ELECTRICAL MANUFACTURING CONFERENCE, 2005, :108-111
[35]   A critical review of the definition of FRA resonance frequency of transformers as per IEEE Std C57.149-2012 [J].
Pramanik, S. ;
Satish, L. .
ELECTRIC POWER SYSTEMS RESEARCH, 2015, 121 :52-57
[36]   Time-Domain Approach to Estimate Series Capacitance of an Isolated Phase Winding of a Transformer [J].
Pramanik, Saurav ;
Satish, L. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (04) :1939-1945
[37]   Estimation of Series Capacitance of a Transformer Winding Based on Frequency-Response Data: An Indirect Measurement Approach [J].
Pramanik, Saurav ;
Satish, L. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2870-2878
[38]   Terminal Measurements-Based Series Capacitance Estimation of Power Transformer Windings Using Frequency-Domain Subspace Identification [J].
Prasanna, K. Lakshmi ;
Samal, Manoj ;
Mondal, Mithun .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2023, 72
[39]   Localization of changes in a model winding based on terminal measurements: Experimental study [J].
Ragavan, K. ;
Satish, L. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (03) :1557-1565
[40]   Transfer function method to diagnose axial displacement and radial deformation of transformer windings [J].
Rahimpour, E ;
Christian, J ;
Feser, K ;
Mohseni, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (02) :493-505