Coordinated Control Strategy of Fault Ride-through for DC Grid Based on Hybrid MMC

被引:0
|
作者
Li, Guoqing [1 ]
Wang, Xiaoxue [1 ]
Jiang, Shouqi [1 ]
Xin, Yechun [1 ]
Wang, Tuo [1 ]
机构
[1] Key Laboratory of Modern Power System Simulation and Control & Renewable Energy Technology, Northeast Electric Power University, Ministry of Education, Jinlin Province, Jilin,132012, China
来源
关键词
DC-DC converters - Electric power system control - Electric power transmission networks - Fault current limiters - Renewable energy;
D O I
10.13335/j.1000-3673.pst.2023.0318
中图分类号
学科分类号
摘要
A DC grid based on a hybrid modular multilevel converter (MMC) effectively achieves large-scale renewable energy integration, multi-energy complementarity, and friendly grid connection. Aiming at the problem that the traditional DC fault ride-through (FRT) scheme will cause the interruption of power transmission in the whole network, a novel DC FRT coordinated control strategy is proposed in this paper, which can quickly interrupt the fault current and avoid the MMC exiting operation. Based on the analysis of fault current composition and key influencing factors, for fault line MMC (FLMMC), a negative voltage control strategy adaptive to the change of fault current is proposed, which can improve the current attenuation speed and ensure reliable fault isolation. For non-fault line MMC (NFLMMC), considering the overvoltage and overcurrent risks of FLMMC, the coordinated current-limiting control method and parameter selection principle of NFLMMC is proposed, where the current-limiting performance can be adaptive to the voltage change of DC bus, to realize the rapid recovery of DC power grid while restraining fault current. Finally, a four-terminal DC grid simulation model is built using the RTLAB OP5600 real-time digital simulation platform. The simulation results show that the coordinated control strategy proposed in this paper can quickly interrupt DC fault current, shorten DC grid recovery time, and improve system security and stability. © 2024 Power System Technology Press. All rights reserved.
引用
收藏
页码:4817 / 4825
相关论文
共 50 条
  • [1] Coordinated Control Strategy of DC Fault Ride-through for the WF Connected to the Grid Through the MMC-HVDC
    Zhu, Bo
    Li, Hongying
    Xu, Panteng
    Jiao, Shi
    Zhang, Lin
    Xin, Yechun
    FRONTIERS IN ENERGY RESEARCH, 2021, 9 (09):
  • [2] AC fault ride-through coordinated control strategy of LCC-MMC hybrid DC transmission system connected to passive networks
    Xin, Yechun
    Lou, Weitao
    Li, Guoqing
    Jiang, Shouqi
    Wang, Tuo
    Yang, Yong
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 131 (131)
  • [3] Design of DC Reactors for DC Fault Ride-through on MMC-based Bipolar DC Grid
    Zhang, Yuhao
    2019 4TH IEEE WORKSHOP ON THE ELECTRONIC GRID (EGRID), 2019, : 606 - 611
  • [4] DC fault current clearance coordinated control strategy for DC grid with hybrid MMC
    Jiang, Shouqi
    Wang, Tuo
    Li, Guoqing
    Xin, Yechun
    Wang, Lixin
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2024, 161
  • [5] A New Hybrid Submodule for MMC with DC Fault Ride-Through Capability
    Rudrasimha, Yedida Ayyappa
    Ghat, Mahendra B.
    Shukla, Anshuman
    2018 IEEE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, DRIVES AND ENERGY SYSTEMS (PEDES), 2018,
  • [6] Voltage equalization modulation strategy for DC fault ride-through of hybrid MMC with minority submodules
    Mei J.
    Zhang S.
    Lei L.
    Guo J.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2023, 43 (11): : 158 - 165
  • [7] DC Pole-to-ground Fault Ride-through Strategy of Hybrid HVDC System Based on LCC and Hybrid MMC
    Zhang D.
    Fan Z.
    Xu H.
    Miao S.
    Wang Y.
    Liu Z.
    Gaodianya Jishu/High Voltage Engineering, 2020, 46 (06): : 2072 - 2080
  • [8] Precharging and DC Fault Ride-Through of Hybrid MMC-Based HVDC Systems
    Zeng, Rong
    Xu, Lie
    Yao, Liangzhong
    Morrow, D. John
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (03) : 1298 - 1306
  • [9] DC fault ride-through control strategy of wind power integrated DC transmission system based on modified MMC
    Jiang S.
    Zhang L.
    Li G.
    Xin Y.
    Wang Z.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2021, 41 (12): : 27 - 35
  • [10] Coordinated Control Strategy of DC Fault Ride-through for Flexible DC Grid-connected System of Wind Power Based on Energy Storage
    Sun Y.
    Lu Y.
    Liu Y.
    Wang Z.
    Li G.
    Wu X.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2023, 47 (03): : 122 - 132