VOLTAGES INDUCED BY LIGHTNING STROKES AND GROUND-FAULTS ON A COAXIAL TELECOM CIRCUIT ENCLOSED IN A COMPOSITE EARTHWIRE. PART I: GENERAL APPROACH AND EARTH FAULTS INDUCED VOLTAGES.
被引:0
作者:
Kouteynikoff, P.
论文数: 0引用数: 0
h-index: 0
机构:
Electricite de France, Clamart, Fr, Electricite de France, Clamart, FrElectricite de France, Clamart, Fr, Electricite de France, Clamart, Fr
Kouteynikoff, P.
[1
]
Anzanel, P.
论文数: 0引用数: 0
h-index: 0
机构:
Electricite de France, Clamart, Fr, Electricite de France, Clamart, FrElectricite de France, Clamart, Fr, Electricite de France, Clamart, Fr
Anzanel, P.
[1
]
机构:
[1] Electricite de France, Clamart, Fr, Electricite de France, Clamart, Fr
来源:
IEEE transactions on power apparatus and systems
|
1985年
/
PAS-104卷
/
04期
关键词:
ELECTRIC GROUNDING - LIGHTNING - TELECOMMUNICATION CABLES;
COAXIAL;
-;
Transients;
D O I:
暂无
中图分类号:
学科分类号:
摘要:
This paper presents the first part of a comprehensive research program about the problem of maximum induced voltages inside a composite coaxial earthwire for overhead transmission lines (the coaxial pair being used as a private telecommunication circuit). Based on the concept of transfer impedance, one can derive a general four-steps calculation procedure valid for both cases of lightning strokes and earth faults. The problem of voltage induced by phase to earth faults is dealt with in Part I where unpublished experimental results on saturation effects in composite earthwire at 50 Hz and a parametric analysis of induced voltages are presented. Practical values of maximum induced voltages are given.