Measurements and vegetational impact of chemical drift from mechanical draft cooling towers

被引:0
|
作者
Rochow, J.J. [1 ]
机构
[1] Dept. Environm. Serv., Consumers Power Co., Jackson, Mich. 49201, United States
来源
Environmental Science and Technology | 1978年 / 12卷 / 13期
关键词
Calcium compounds - Environmental impact - Sulfur compounds - Water cooling towers;
D O I
暂无
中图分类号
学科分类号
摘要
Collection and analyses of precipitation prior to and after cooling tower operation at the Palisades Plant in southwestern Michigan resulted in high deposition rates of sulfate and calcium up to 92 m from the towers. Sulfate deposition rates during operation averaged up to 9. 0 g m** minus **2 month** minus **1 in areas within 50 m of the cooling towers and decreased to 0. 61 g m** minus **2 month** minus **1 between 700 and 1609 m. Calcium deposition rates during operation averaged up to 4. 5 g m** minus **2 month** minus **1 in areas within 50 m of the cooling towers and decreased to 0. 57 g m** minus **2 month** minus **1 between 700 and 1609 m. The high sulfate deposition rates were assumed to be responsible for severe vegetation damage within 92 m of the cooling towers.
引用
收藏
页码:1379 / 1383
相关论文
共 50 条
  • [22] A novel approach for performance assessment of mechanical draft wet cooling towers
    Naik, B. Kiran
    Muthukumar, P.
    APPLIED THERMAL ENGINEERING, 2017, 121 : 14 - 26
  • [23] A new algorithm for optimum design of mechanical draft wet cooling towers
    Department of Energy Engineering, Graduate School of the Environment and Energy, Islamic Azad University, P.O. Box 14515-775, Tehran, Iran
    不详
    不详
    J. Appl. Sci., 2009, 3 (561-566): : 561 - 566
  • [24] MEASUREMENTS OF NOISE FROM COOLING TOWERS
    MILLER, L
    DYER, I
    JOURNAL OF THE ACOUSTICAL SOCIETY OF AMERICA, 1956, 28 (04): : 758 - 758
  • [25] NUMERICAL MODELING OF WET COOLING-TOWERS .2. APPLICATION TO NATURAL AND MECHANICAL DRAFT TOWERS
    MAJUMDAR, AK
    SINGHAL, AK
    REILLY, HE
    BARTZ, JA
    JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1983, 105 (04): : 736 - 743
  • [26] PERSISTENCE OF PLUMES FROM NATURAL DRAFT COOLING-TOWERS
    BARBER, FR
    MARTIN, A
    SHEPHERD, JG
    SPURR, G
    ATMOSPHERIC ENVIRONMENT, 1974, 8 (04) : 407 - 418
  • [27] MINIMUM SIZE OF LARGE DRY COOLING TOWERS WITH COMBINED MECHANICAL AND NATURAL DRAFT
    MOORE, FK
    JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1973, 95 (03): : 383 - 389
  • [28] Electrical-fluid dynamic performance of mechanical draft water cooling towers
    Sirena, Jose A.
    APPLIED THERMAL ENGINEERING, 2013, 54 (01) : 185 - 189
  • [29] MINLP optimization of mechanical draft counter flow wet-cooling towers
    Serna-Gonzalez, Medardo
    Ponce-Ortega, Jose M.
    Jimenez-Gutierrez, Arturo
    CHEMICAL ENGINEERING RESEARCH & DESIGN, 2010, 88 (5-6A): : 614 - 625
  • [30] A Novel Approach for Water Conservation and Plume Abatement in Mechanical Draft Cooling Towers
    Wang, Weishu
    Ge, Xuewen
    Zhao, Shifei
    Zheng, Haonan
    Xu, Weihui
    Lv, Jiatong
    Zhu, Ge
    ATMOSPHERE, 2019, 10 (12)