Coordinate control strategy for 10 MW high temperature gas-cooled reactor

被引:0
作者
Yan, Yong [1 ]
Du, Jihong [1 ]
Feng, Yuankun [1 ]
机构
[1] Dept. of Automat., Tsinghua Univ., Beijing 100084, China
来源
Qinghua Daxue Xuebao/Journal of Tsinghua University | 2001年 / 41卷 / 10期
关键词
Computer control systems - Control equipment - Coordination reactions - High temperature reactors - Proportional control systems;
D O I
暂无
中图分类号
学科分类号
摘要
The 10 MW high temperature gas-cooled reactor (HTR-10) has many new characteristics and complex dynamics. An automatic control system and four coordinate control strategies were designed for HTR-10. A practical tuning method is given with the evaluation of the four strategies at a typical set point with many perturbances. The strategy in which the helium temperature is controlled by the nuclear power and the steam temperature is controlled by the helium flow is recommended as the best control strategy.