A substation is a complex system composed of a series of different types of electrical equipment interconnected by conductors. In order to study the seismic performance of substation as a whole system, this paper proposed a new system analysis method combining graph theory, fault tree and success path. In the proposed method, a directed graph logic model of the entire substation was built based on the location and connection logic relationship of each electrical equipment and the power transmission path in the substation. Regarding the number of out-lines that can function normally as the performance evaluation index of the substation, the seismic vulnerability analysis of the substation can be obtained based on the seismic vulnerability curve at the device level by the Monte Carlo simulation method. A case study was carried out on a typical 220kV substation by this method and vulnerable points of seismic resistance of the substation system were pointed out through sensitive analysis. © 2020 Chin. Soc. for Elec. Eng.
引用
收藏
页码:7773 / 7781
页数:8
相关论文
共 25 条
  • [1] Xie Qiang, State-of-the-art of seismic disaster research and emergency response of electric power system, Electric Power Construction, 29, 8, pp. 1-6, (2008)
  • [2] Yu Yongqing, Li Guangfan, Li Peng, Et al., Investigation and analysis of electric equipment damage in Sichuan power grid caused by Wenchuan earthquake, Power System Technology, 32, 11, pp. 5-10, (2008)
  • [3] Schiff A J, Tang A K., Chi-Chi, Taiwan, earthquake of September 21, 1999: lifeline performance, (1999)
  • [4] Eidinger J, Davis C, Tang A, Et al., M 9.0 Tohoku earthquake March 11 2011 performance of water and power systems, (2012)
  • [5] Liu Rushan, Liu Jinlong, Yan Dongqi, Et al., Seismic damage investigation and analysis of electric power system in Lushan Ms 7.0 earthquake, Journal of Natural Disasters, 22, 5, pp. 83-90, (2013)
  • [6] 2, pp. 5-10
  • [7] Ouyang Min, Wang Zhenghua, Resilience assessment of interdependent infrastructure systems: With a focus on joint restoration modeling and analysis, Reliability Engineering & System Safety, 141, pp. 74-82, (2015)
  • [8] Wen Ruizhi, Tao Xiaxin, Xie Lili, Earthquake damage analysis of coupling lifeline systems, Journal of Natural Disasters, 9, 2, pp. 105-110, (2000)
  • [9] Bie Zhaohong, Lin Yanling, Qiu Aici, Concept and research prospects of power system resilience, Automation of Electric Power Systems, 39, 22, pp. 1-9, (2015)
  • [10] Mosalam K M, Gunay S., Seismic performance evaluation of high voltage disconnect switches using real-time hybrid simulation: I.System development and validation, Earthquake Engineering & Structural Dynamics, 43, 8, pp. 1205-1222, (2014)