Optimal design and application of energy storage system in Dongfushan island stand-alone microgrid

被引:0
作者
机构
[1] Zhejiang Electric Power Corporation Research Institute
来源
Zhao, B. (zhaobozju@163.com) | 1600年 / Automation of Electric Power Systems Press卷 / 37期
关键词
Energy storage system; Engineering application; Microgrid; Operation parameter; Optimal configuration; Technology selection;
D O I
10.7500/AEPS201208166
中图分类号
学科分类号
摘要
To solve the electricity and water consumption problems, a techno-economic research on wind-solar-diesel-storage isolated microgrid is made based on the engineering practice on Dongfushan Island. The paper focuses on the technology selection, optimal design and operation parameters optimization of the energy storage system in the Dongfushan stand-alone microgrid. By considering the technical, economic, security and maturity aspects, the option of improved valve-regulated lead-acid battery is chosen as the best solution for currently available technologies of energy storage. In the energy storage optimization configuration, multi-objective design is made with minimizing the operation time of diesel generator, maximizing the utilization of renewable energy, and maximizing the lifetime of the energy storage system as the optimization objectives. As for the selection of the energy storage system's operation parameters, by referring to the coordinated operation control strategy, the terminal voltage of battery banks is adopted as the standard to do the mode control, mode switch and storage system protection. The operation parameters are optimally selected to ensure that the microgrid operates orderly, efficiently and reliably. The actual operation analysis demonstrates the practicability and effectiveness of the research method. © 2013 State Grid Electric Power Research Institute Press.
引用
收藏
页码:161 / 167
页数:6
相关论文
共 16 条
[11]  
Katti P.K., Khedkar M.K., Alternative energy facilities based on site matching and generation unit sizing for remote area power supply, Renewable Energy, 32, 8, pp. 1346-1362, (2007)
[12]  
Xu D., Ding Q., Pan Y., Et al., Study on optimizing capacity of storage battery in microgrid system based on economic dispatch, Power System Protection and Control, 39, 17, pp. 55-59, (2011)
[13]  
Mei S., Wang Y., Liu F., A game theory based planning model and analysis for hybrid power system with wind generators-photovoltaic panels-storage batteries, Automation of Electric Power Systems, 35, 20, pp. 13-19, (2011)
[14]  
Rodolfo D.L., Jose L.B.A., Jose M.Y.L., Et al., Multi-objective optimization minimizing cost and life cycle emissions of stand-alone PV-wind-diesel systems with batteries storage, Applied Energy, 88, 11, pp. 4033-4041, (2011)
[15]  
Ma X., Wu Y., Fang H., Et al., Optimal sizing of hybrid solar-wind distributed generation in an islanded microgrid using improved bacterial foraing algorithm, Proceedings of the CSEE, 31, 25, pp. 17-25, (2011)
[16]  
Chen S.X., Gooi H.B., Wang M.Q., Sizing of energy storage for microgrids, IEEE Trans on Smart Grid, 3, 1, pp. 142-151, (2012)