Bimetallic corrosion of copper tube in brazing part

被引:0
作者
Yamate, Toshihiro [1 ]
机构
[1] Technical Research Laboratory, Takenaka Corporation, Inzai, Tiba 270-1395, 1-5-1, Otuka
来源
Zairyo to Kankyo/ Corrosion Engineering | 2007年 / 56卷 / 04期
关键词
Bimetallic corrosion; Brazing; Copper tube; Natural electrode potential; Solder;
D O I
10.3323/jcorr.56.170
中图分类号
学科分类号
摘要
On the brazing part of copper tube and U bend in the fan coil unit, the solder was not corroded, and the soft copper tube that touches the solder has been corroded one-sidedly. Natural electrode potential of the solder and natural electrode potential of copper were measured on an unused brazing part sample in the tap water. The potential of the solder was about 100 mV higher than the potential of copper. It is guessed that the cause of corrosion is a bimetallic corrosion of which the solder is cathode and copper is anode.
引用
收藏
页码:170 / 174
页数:4
相关论文
共 1 条
  • [1] Takasaki S., Proc. 25th Jpn. Corrosion Conf, (2001)