Ventilation condition effects on heat dissipation of the lithium-ion battery energy storage cabin fire

被引:1
作者
Wang, Jie [1 ,3 ,4 ]
Yang, Meilin [1 ,3 ,4 ]
Lu, Kaihua [2 ]
机构
[1] Wuhan Univ Sci & Technol, Sch Resource & Environm Engn, 947 Heping Ave, Wuhan 430081, Hubei, Peoples R China
[2] China Univ Geosci Wuhan, Fac Engn, Wuhan 430074, Hubei, Peoples R China
[3] Wuhan Univ Sci & Technol, Safety & Emergency Inst, Wuhan 430081, Hubei, Peoples R China
[4] Hubei Key Lab Efficient Utilizat & Agglomerat Meta, Wuhan 430081, Hubei, Peoples R China
基金
中国国家自然科学基金;
关键词
Lithium-ion battery module; Thermal runaway fire; Ventilation condition; Heat dissipation efficiency;
D O I
10.1016/j.csite.2024.105373
中图分类号
O414.1 [热力学];
学科分类号
摘要
Due to the high energy density of the lithium-ion battery, lots of heat, smoke, and toxic gas will be rapidly produced during thermal runaway and accumulate at the extreme cabin temperature. Therefore, a lithium-ion battery energy storage cabin requires an efficient ventilation condition to ensure fire safety. This work investigates the effects of ventilation mode, ventilation position, and ventilation speed on the heat dissipation inside the cabin. The results indicate that under an optimal ventilation condition, the cabin can achieve excellent heat dissipation efficiency. With the change of ventilation mode, it is found that when the combination of mechanical and natural ventilation is used for smoke evacuation, the average temperature in the cabin can be decreased by about 20 degrees C. In addition, when an air exhaust vent is set at the top center of this cabin, the maximum temperature can be reduced from 810 degrees C to 620 degrees C. Finally, as the ventilation velocity raised from 1 m/s similar to 10 m/s, the average temperature inside the cabin decreased linearly. Particularly, at the ventilation velocity of 6 m/s, the average temperature can be approximately controlled in the range of 40-80 degrees C, and the heat dissipation efficiency can reach 62.17 %.
引用
收藏
页数:11
相关论文
共 36 条
[1]   Numerical study on the fire and its propagation of large capacity lithium-ion batteries under storage [J].
Cui, Yilin ;
Chen, Yin ;
Chen, Mingyi ;
Ouyang, Dongxu ;
Weng, Jingwen ;
Tao, Changfa ;
Zhao, Luyao ;
Wang, Jian .
JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2023, 148 (12) :5787-5803
[2]   Effect of finned networks on PCM based battery thermal management system for cylindrical Li-ion batteries [J].
Dey, Hrishav ;
Pati, Sukumar ;
Randive, Pitambar R. ;
Baranyi, Laszlo .
CASE STUDIES IN THERMAL ENGINEERING, 2024, 59
[3]  
Du Shengyin, 2022, Electric Power Eng. Technol., V41, P58
[4]  
Feng X., 2016, Thermal Runaway Initiation and Propagation of lithium-Ion Traction Battery for Electric Vehicle: Test, Modeling and Prevention
[5]   Numerical analysis of smoke dispersion against the wind in a tunnel fire [J].
Gannouni, Soufien ;
Ben Maad, Rejeb .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2016, 158 :61-68
[6]   Effect of air inlet and outlet cross sections on the cooling system of cylindrical lithium battery with segmental arrangement utilized in electric vehicles [J].
Hai, Tao ;
Said, Nejla Mahjoub ;
Cheraghian, Goshtasp ;
Zhou, Jincheng ;
Malekshah, Emad Hasani ;
Sharifpur, Mohsen .
JOURNAL OF POWER SOURCES, 2023, 553
[7]   Ceiling jet velocity during the whole process of fire development in a tunnel [J].
He, Lu ;
Xu, Zhisheng ;
Markert, Frank ;
Zhao, Jiaming ;
Xie, En ;
Liu, Qiulin ;
Fan, Chuangang .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2021, 212 (212)
[8]   Model scale railcar fire tests [J].
Ingason, Haukur .
FIRE SAFETY JOURNAL, 2007, 42 (04) :271-282
[9]   A coupled conjugate heat transfer and CFD model for the thermal runaway evolution and jet fire of 18650 lithium-ion battery under thermal abuse [J].
Kong, Depeng ;
Wang, Gongquan ;
Ping, Ping ;
Wen, Jennifer .
ETRANSPORTATION, 2022, 12
[10]  
LAW M, 1978, ENG J AISC, V15, P59