Short Circuit Current Calculation of Power System With DFIG Wind Turbines

被引:0
作者
Zhang J. [1 ]
Chen L. [1 ]
Wang C. [2 ]
Zhang B. [1 ]
Hao Z. [1 ]
机构
[1] School of Electrical Engineering, Xi'an Jiaotong University, Xi'an, 710049, Shaanxi
[2] Electric Power Research Institute, State Grid Jiangsu Electric Power Co., Ltd., Nanjing, 211103, Jiangsu
来源
Dianwang Jishu/Power System Technology | 2019年 / 43卷 / 03期
关键词
DFIG; Fault equivalent model; Low voltage ride-through control; Short circuit current; Wind power generation;
D O I
10.13335/j.1000-3673.pst.2018.0666
中图分类号
学科分类号
摘要
When a fault occurs in the power system with multiple DFIGs (doubly-fed induction generators), the control scheme and short circuit calculation model of the DFIGs are not all the same, thus affecting short circuit current distribution in the power system. This paper proposes a short circuit calculation method for the power system, involving the determination process of the DFIG control schemes. The control scheme of a DFIG mainly depends on its terminal voltage drop. In this paper, the influence of DFIG fault models under continuous excitation control and crowbar protection control on fault voltage distribution for the power system with a radial wiring structure is analyzed. According to the obtained voltage distribution characteristics, a determination method for the post-fault control schemes of the DFIGs is proposed. Then, by contrast with the system based on conventional synchronous generators, the node voltage equations and short circuit calculation program chart for the power system with DFIGs are given. At last, a power system with 6 DFIGs is simulated to verify effectiveness of the proposed determination method for DFIG control scheme and the short circuit calculation method. © 2019, Power System Technology Press. All right reserved.
引用
收藏
页码:887 / 894
页数:7
相关论文
共 19 条
  • [1] Yang G., Li X., Zhou Z., Impacts of wind farm on relay protection for distribution network and its countermeasures, Power System Technology, 33, 11, pp. 87-103, (2009)
  • [2] Tong N., Lin X., Li Z., Et al., Study for reciprocal effect between overcurrent protection and doubly-fed induction generator feeding current under the condition of symmetrical voltage sag, Proceedings of the CSEE, 34, 22, pp. 3806-3814, (2014)
  • [3] Bi T., Li Y., Ma L., Et al., Configuration and setting of relay protection for wind farm and its outgoing line, Power System Protection and Control, 42, 5, pp. 45-50, (2014)
  • [4] Wang J., Tai N., Song K., Et al., Penetration level permission of DG in distributed network considering relay protection, Proceedings of the CSEE, 30, 22, pp. 37-43, (2010)
  • [5] Mohsen R., Mostafa P., Grid-fault ride-through analysis and control of wind turbines with doubly fed induction generators, Electric Power Systems Research, 80, pp. 184-195, (2010)
  • [6] Wang C., Song G., Chi Y., Et al., Fault characteristics analysis of wind power system, Automation of Electric Power Systems, 39, 21, pp. 52-58, (2015)
  • [7] Xiang D., Yang S., Ran L., Ride-through control strategy of a doubly fed induction generator for symmetrical grid fault, Proceedings of the CSEE, 26, 3, pp. 164-170, (2006)
  • [8] Wang H., Zhang W., Hu J., Et al., A control strategy for doubly-fed induction generator wind turbines under asymmetrical grid voltage conditions caused by faults, Automation of Electric Power Systems, 34, 4, pp. 97-102, (2010)
  • [9] Ma W., Application of Crowbar circuit in grid fault riding through for doubly-fed induction wind power generation system, Electric Power Automation Equipment, 31, 7, pp. 127-130, (2011)
  • [10] Huang T., Lu Y., Analysis on transient EMF variation characteristic of doubly fed induction generator after crowbar protection activated, Power System Technology, 38, 10, pp. 2759-2765, (2014)