Generalized APF based on three-level inverter

被引:0
作者
Xue, Chang [1 ]
Wang, Jianze [1 ]
Ji, Yanchao [1 ]
机构
[1] School of Electrical Engineering and Automation, Harbin Institute of Technology, Harbin 150001, China
来源
Dianli Zidonghua Shebei/Electric Power Automation Equipment | 2012年 / 32卷 / 09期
关键词
Vector spaces - Modulation - Active filters - Bandpass filters - Electric inverters - Reactive power;
D O I
暂无
中图分类号
学科分类号
摘要
A GAPF(Generalized Active Power Filter) based on three-level inverter is proposed, which has higher equivalent switching frequency and voltage level, suitable for high power applications. Its topology, operating principle and control method are discussed. Because the selective harmonic elimination technique is poor in real-time performance and neutral-point voltage adjustment, the space vector modulation technique is adopted. In order to precisely balance the DC-side capacitor voltages of three-level inverter, a method is proposed to quantitatively calculate the duty cycle of small vector. Simulative results show that, three-level GAPF can effectively realize the functions of reactive power compensation, harmonics suppression and negative sequence filtering and greatly reduce the capacity of grid-side filtering reactor.