Control of VSC-HVDC in AC/DC hybrid transmission with wind farms integrated

被引:0
|
作者
机构
[1] School of Electric Power Engineering, South China University of Technology, Guangzhou , 510641 , Guangdong Province
[2] Electric Power Research Institute, China Southern Power Grid, Guangzhou , 510080 , Guangdong Province
来源
Fan, Xinming | 1600年 / Chinese Society for Electrical Engineering卷 / 34期
关键词
AC/DC hybrid transmission; Control strategy; HVDC transmission; Stability; Voltage source converter (VSC); Wind power;
D O I
10.13334/j.0258-8013.pcsee.2014.28.005
中图分类号
学科分类号
摘要
This paper proposed a more flexible control strategy for voltage source converter based high voltage direct current (VSC-HVDC) transmission to improve the performance of the AC/DC hybrid transmission systems with wind farms integrated. A novel AC voltage and load angle control approach was designed for the wind farm side VSC. In AC/DC hybrid transmission mode, constant active power control was achieved by regulating the load angle between the voltage of wind farm AC bus and the output voltage of wind farm side VSC. In simplex VSC-HVDC transmission mode, the voltage of wind farm AC bus was automatically modulated to have constant amplitude and constant frequency to achieve the synchronous transmission of fluctuating wind power. The control approach requires no switching control actions to accommodate mode change. Moreover, damping to resonances in the system was improved by additional high-pass filter. A new direct current vector control approach was applied to the grid side VSC to regulate the DC voltage to reference value. The AC/DC hybrid transmission systems connected wind farms equipped with squirrel cage induction generator (SCIG) and doubly fed induction generator (DFIG) were respectively modeled and simulated by PSCAD/EMTDC. The simulation results considering a series of operation conditions prove the validity and feasibility of the proposed approaches. ©2014 Chinese Society for Electrical Engineering
引用
收藏
页码:4781 / 4790
页数:9
相关论文
共 23 条
  • [11] Qiu D., Li Q., Nan X., Direct power control of VSC-HVDC system under unsymmetrical fault of grid, High Voltage Engineering, 38, 4, pp. 1012-1018, (2012)
  • [12] Moharana A., Dash P.K., Input-output linearization and robust sliding-mode controller for the VSC-HVDC transmission link, IEEE Transactions on Power Delivery, 25, 3, pp. 1952-1961, (2010)
  • [13] Guan M., Xu Z., Modeling and control of modular multilevel converter in HVDC transmission , Automation of Electric Power Systems, 34, 19, pp. 64-68, (2010)
  • [14] Dierckxsens C., Srivastava K., Reza M., Et al., A distributed DC voltage control method for VSC MTDC systems , Electric Power Systems Research, 82, 1, pp. 54-58, (2012)
  • [15] Ruan S., Li G., Jiao X., Et al., Adaptive control design for VSC-HVDC systems based on backstepping method, Electric Power Systems Research, 77, 6, pp. 559-565, (2007)
  • [16] Li S., Wang Z., Wang G., Et al., PID neural network sliding-mode controller for three-level offshore wind power VSC-HVDC converter , Proceedings of the CSEE, 32, 4, pp. 20-28, (2012)
  • [17] Wang C., Yu B., Xiao J., Et al., Sizing of energy storage systems for output smoothing of renewable energy systems, Proceedings of the CSEE, 32, 16, pp. 1-8, (2012)
  • [18] Albadi M.H., El-Saadany E.F., Overview of wind power intermittency impacts on power systems, Electric Power Systems Research, 80, 6, pp. 627-632, (2010)
  • [19] Fan X., Guan L., He J., Constant active power and frequency auxiliary control for multilevel VSC-HVDC power transmission, Power System Technology, 36, 9, pp. 182-186, (2012)
  • [20] Liserre M., Cardenas R., Molinas M., Overview of multi-MW wind turbines and wind parks, IEEE Transactions on Industrial Electronics, 58, 4, pp. 1081-1092, (2011)