Analysis of control strategy for grid-connected inverter under different constraints based on asymmetric grid

被引:0
作者
Jiang, Weidong [1 ]
Wu, Zhiqing [1 ]
Hu, Yang [1 ]
Tao, Ziran [1 ]
机构
[1] School of Electrical and Automation Engineering, Hefei University of Technology, Hefei
来源
Dianli Xitong Zidonghua/Automation of Electric Power Systems | 2015年 / 39卷 / 19期
基金
中国国家自然科学基金;
关键词
Asymmetric grid; Control strategy; Grid-connected inverter; Positive and negative sequence separation; Repetitive control;
D O I
10.7500/AEPS20140307009
中图分类号
学科分类号
摘要
When a three-phase grid is unbalanced, the grid-connected inverter based on the traditional double-loop control strategy will generate even-numbered and odd-numbered harmonics on the DC side and AC side, respectively, which will seriously affect the performance of the grid-connected inverter system. For this reason, the control strategy of grid connection is proposed to realize under the positive-negative sequence rotational coordinate system. With the control strategy, different constraint conditions are obtained from different control objectives (inner current reference) and the corresponding control method is designed. To effectively and rapidly separate positive and negative sequences, an instantaneous positive-negative sequence separating method is presented. The forgetting integration algorithm is adopted for filtering. Experimental results under various control objectives are compared to show the effectiveness and simplicity of the algorithm. ©2015 Automation of Electric Power Systems Press
引用
收藏
页码:113 / 120and136
相关论文
共 17 条
[1]  
Rioual P., Pouliquen H., Louis J.P., Regulation of a PWM rectifier in the unbalanced network state using a generalized model, IEEE Trans on Power Electronics, 11, 3, pp. 495-502, (1996)
[2]  
Zhao X., Jin X., Zhou F., Et al., Unbalanced control of grid-connected inverters based on proportion integration reduced order resonant controllers, Proceedings of the CSEE, 33, 19, pp. 84-92, (2013)
[3]  
Wu X.H., Panda S.K., Xu J.X., Analysis of the instantaneous power flow for three-phase PWM Boost rectifier under unbalanced supply voltage conditions, IEEE Trans on Power Electronics, 23, 4, pp. 1679-1691, (2008)
[4]  
Chen H., Wang X., Liu J., Parallel connection control method for the PWM rectifiers under unbalanced power grid voltage conditions, Electric Machines and Control, 13, 5, pp. 702-707, (2009)
[5]  
Hu J., He Y., Guo X., Et al., Modeling and control of the DFIG based wind-power generation system under unbalanced grid voltage conditions, Automation of Electric Power Systems, 31, 14, pp. 47-56, (2007)
[6]  
Li Z., Wang P., Li Y., Et al., Instantaneous power based control of three-phase PWM rectifier under distorted source voltages, Proceedings of the IEEE International Symposium on Industrial Electronics (ISIE'09), pp. 1234-1239, (2009)
[7]  
Zhang J., Li X., Hou G., Et al., Study of sliding-mode control based grid-side PWM rectifier for wind power generation system under unbalanced input voltage condition, Proceedings of the 4th IEEE Conference on Industrial Electronics and Applications (ICIEA'09), pp. 1631-1635, (2009)
[8]  
Escobar G., Martinez-Montejano M.F., Torres Olguin R., Et al., An adaptive direct power control for three-phase PWM rectifier in the unbalanced case, Proceedings of the IEEE 39th Power Electronics Specialists Conference (PESC'08), pp. 3150-3155, (2008)
[9]  
Zhang X., Ji J., Zhang C., Et al., Study of internal model control based three-phase PWM rectifier under unbalanced input voltage condition, Proceedings of the CSEE, 25, 13, pp. 51-56, (2005)
[10]  
Xu H., Zhang W., Hu J., Et al., Synchronizing signal detection of fundamental voltage under unbalanced and/or distorted grid voltage conditions, Automation of Electric Power Systems, 36, 5, pp. 90-95, (2012)