Audible noise spectrum characteristics of positive and negative wire in UHV corona cage

被引:0
|
作者
Liu, Yuanqing [1 ]
Guo, Jian [1 ]
Lu, Jiayu [1 ]
机构
[1] China Electric Power Research Institute, Beijing 100192, Haidian District
来源
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering | 2014年 / 34卷 / 18期
关键词
Audible noise; Corona cage; Cumulative probability; Spectrum; UHVDC transmission line;
D O I
10.13334/j.0258-8013.pcsee.2014.18.014
中图分类号
学科分类号
摘要
For further study of the discharge mechanism and audible noise's characteristics of positive, negative and bipolar UHVDC test line, the audible noise's spectrum for 6×720 mm2 wires were tested and analyzed based on the corona cage in the UHV-DC test base of State Grid Corporation of China. Using the mid-net detachable corona cage, the audible noise of positive, negative and bipolar lines in corona cage were tested, and the noise's spectral characteristics of positive, negative line and that near the bipolar pole, and their relationship with voltage were reached, and the comparative analysis of their results were conducted. The paper also analyzed the stability of corona audible noise's A weighed sound level and its 8 kHz components in different surface field strength when the background noise was also considered. Finally, the 8 kHz component method which was proposed before being used to analyze the noise's characteristics of positive, negative pole and the noise near dipole line in different surface field strength, and the 8 kHz component can be used to calculate the noises of positive and dipole line. © 2014 Chin. Soc. for Elec. Eng.
引用
收藏
页码:2976 / 2982
页数:6
相关论文
共 23 条
  • [1] Liu Z., Electromagnetic Environment of UHV DC Power Transmission Project, pp. 1-50, (2009)
  • [2] Shu Y., Zhang W., Research of key technologies for UHV transmission, Proceedings of the CSEE, 27, 31, pp. 1-6, (2007)
  • [3] Zhang W., Yu Y., Li G., Et al., Researches on UHVDC technology, Proceedings of the CSEE, 27, 22, pp. 1-7, (2007)
  • [4] Wu G., Electromagnetic environment problem brought about by ±500 kV DC transmission project in China, Power System Technology, 29, 11, pp. 5-8, (2005)
  • [5] Shu Y., Liu Z., Yuan J., A survey on demonstration of UHV power transmission by State Grid Corporation of China in the year of 2005, Power System Technology, 30, 5, pp. 1-12, (2006)
  • [6] Zhang W., Lu J., Ju Y., Et al., Design consideration of conductor bundles of ±800 kV DC transmission lines, Proceedings of the CSEE, 27, 27, pp. 1-6, (2007)
  • [7] Zhou H., Yu Y., Discussion on several important problems of developing UHV AC transmission in China, Power System Technology, 29, 12, pp. 1-9, (2005)
  • [8] Nakano Y., Fukushima M., Statistical audible noise performance of Shiobara HVDC test line, IEEE Transactions on Power Delivery, 5, 1, pp. 290-296, (1990)
  • [9] Comber M.G., Zaffanella L.E., The use of single-phase overhead test lines and test cages to evaluate the corona effects of EHV and UHV transmission lines, IEEE Transactions on Power Apparatus and Systems, 93, 1, pp. 81-90, (1974)
  • [10] Dallaire R.D., Sarma M.P., Rivest N., HVDC monopolar and bipolar cage studies on the corona performance of conductor bundles, IEEE Transactions on Power Apparatus and Systems, 103, 1, pp. 84-91, (1984)