Research on Harmonic Overvoltage of Cable Sheath on 220kV Side of Electric Railway Traction Station

被引:0
|
作者
Cao J. [1 ]
Chen J. [1 ]
Tan X. [1 ]
Li C. [1 ]
Zhang W. [1 ]
Fang C. [2 ]
Zhuang L. [2 ]
Zhang Y. [2 ]
Li F. [2 ]
机构
[1] State Grid Jiangsu Electric Power Research Institute, Nanjing
[2] College of Electrical Engineering and New Energy, Three Gorges University, Hubei, Yichang
关键词
Cable sheath; Influencing factors; Over voltage; Railway harmonics;
D O I
10.2478/amns.2023.1.00240
中图分类号
学科分类号
摘要
The special operation mode of high-speed railway will generate a large amount of harmonics. The harmonics will be transmitted to the 220kV side high-voltage cables through the traction transformer, and harmonic voltages will be generated on the cable sheath, threatening the safe operation of the cables. In this paper, on the basis of the measured harmonic data of the traction substation, a harmonic source model based on the measured data is established, which solves the complex problem of harmonic source modeling and can accurately reflect the actual operating conditions of high-speed trains. On this basis, the harmonic voltage characteristics of the cable sheath on the 220kV side of the high-speed railway under the three working conditions of traction, regenerative braking and inertia are simulated and calculated, and the effects of cable length, cable grounding method, and harmonic current parameters on the harmonic voltage are explored. Affect the law. The results show that under different operation modes of high-speed rail, the harmonic voltage of the sheath far exceeds the normal operation of the power frequency, and the maximum value of the harmonic voltage of the cable sheath can reach 454V under the traction condition; Under working conditions, the overvoltage of the metal sheath is greatly affected by the grounding method of the cable, the length of the cable and the harmonic current content. The above research results have important reference significance for the safe operation of electrified railways. © 2023 Jinying Cao et al.;published by Sciendo.
引用
收藏
相关论文
共 8 条
  • [1] Harmonic Suppression of 220kV Gong Ping power station
    Li Wei
    Chen Jian
    2008 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION, VOLS 1 AND 2, 2009, : 383 - +
  • [2] Simulation of neutral point overvoltage and research on new protection measures for 220kV transformer
    Chen Xiujuan
    Xia Chao
    Wu Guoxing
    Zhang Fan
    Ji Huizheng
    Wang Jianmin
    Shi Weidong
    Chen Long
    Lu Tiantian
    Lei Ting
    Zhang Zhaohua
    2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019), 2019, : 582 - 587
  • [3] Electric Railway Loufan Traction Station Of Shanxi Power Grid Harmonic Impact Analysis
    Cao, Mingde
    Wang, Jinhao
    Lei, Da
    Yang, Chaoying
    Feng, Lei
    Yao, Lei
    Sun, Weiqing
    PROCEEDINGS OF THE 2016 5TH INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY AND ENVIRONMENT ENGINEERING (ICSEEE 2016), 2016, 63 : 569 - 573
  • [4] Estimation of Electric Field Distribution in a 220KV HVAC XLPE Cable under Differential Ageing
    Pandey, Priyesh kumar
    Kumar, Azmeera Harshith
    Reddy, C.C.
    Proceedings of the International Symposium on Electrical Insulating Materials, 2023, : 364 - 367
  • [5] Research on the Design Method of Railway Traction Power Supply Cable under Harmonic Restraint
    Jin Qingren
    Guo Min
    Chen Weidong
    2018 IEEE 15TH INTERNATIONAL CONFERENCE ON NETWORKING, SENSING AND CONTROL (ICNSC), 2018,
  • [6] Protection performance assessments of two types of sheath voltage limiters in 220kV single point bonded cable system
    Li, Quanxin
    Xue, Jian
    Wang, Jianguo
    Xiao, Jing
    Fan, Yadong
    Zhou, Mi
    Cai, Li
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 212
  • [7] Research On The Over-voltage of 220kV Power System Caused by Traction Transformer's Commissioning
    Ma Weiping
    Cheng Fangxiao
    Zhou Wenjun
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 1817 - +
  • [8] Research on overvoltage and minimum air clearance on 1000kV AC side of converter transformer in ±1100kV Guquan converter station
    Lou Ying
    Li Zhenqiang
    Xie Liang
    Wan Lei
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2159 - 2164