Design of sub-synchronous oscillation proportional resonance damping controller for doubly-fed wind turbines based on impedance analysis

被引:0
作者
Qin, Shiyao [1 ]
Wang, Zehui [2 ,3 ]
Li, Shaolin [1 ]
Chen, Renjie [3 ,4 ]
Jia, Lingjie [2 ,3 ]
Peng, Xiaotao [2 ,3 ]
机构
[1] China Elect Power Res Inst, Beijing, Peoples R China
[2] Wuhan Univ, Sch Elect Engn & Automat, Hubei Key Lab Power Equipment & Syst Secur Integra, Wuhan, Peoples R China
[3] Wuhan Univ, Sch Elect Engn & Automat, Wuhan, Peoples R China
[4] Wuhan Iron & Steel Design & Res Inst, Wuhan, Peoples R China
关键词
Sub-synchronous oscillation; Parameter tuning; Doubly fed induction generators; Oscillation monitoring; Damping control; FARMS;
D O I
10.1016/j.ijepes.2024.110333
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Doubly fed induction generators are widely used in wind power generation because of their efficient and low-cost power generation and active-reactive power decoupling control features. For the problem of sub-synchronous oscillation generated by the grid-connected doubly-fed wind turbine through series compensation line, this paper firstly carries out the eigenvalue participation factor analysis of the small signal model including the multiphysical control links of grid-connected system, and an impedance model is constructed for the quantitative analysis of the sub-synchronous oscillation damping characteristics. Applying impedance analysis on the above model, it is concluded that the negative equivalent resistance under the resonant frequency is the cause of subsynchronous oscillation. Then a controller was designed that uses a high-pass filter in series with a proportionalresonant link to generate an additional oscillation damping component in the rotor winding modulation voltage. Based on the analysis of how controller parameters affect the impedance characteristics, the inequality constraint conditions for the parameter design to optimize the controller's impedance compensation characteristics and robustness to oscillation frequency is proposed. Finally, the oscillation suppression effect of the controller is analyzed by time domain simulation and it is tested that the controller can suppress sub-synchronous oscillation and has adaptability in scenarios with different parameters.
引用
收藏
页数:18
相关论文
共 19 条
[1]   STABILITY SIMULATION OF WIND TURBINE SYSTEMS [J].
ANDERSON, PM ;
BOSE, A .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (12) :3791-3795
[2]   Analytical assessment of subsynchronous resonance (SSR) impact on doubly fed induction generator wind turbine behavior and efficient suppression of SSR oscillations [J].
Azizi, Amir Hossein ;
Rahimi, Mohsen .
INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2021, 31 (03)
[3]   Suppression of Sub-Synchronous Resonances Through Excitation Control of Doubly Fed Induction Generators [J].
Baesmat, Hana Jannaty ;
Bodson, Marc .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2019, 34 (06) :4329-4340
[4]  
[曹建春 Cao Jianchun], 2019, [电网技术, Power System Technology], V43, P895
[5]   PI Parameter Tuning of Converters for Sub-Synchronous Interactions Existing in Grid-Connected DFIG Wind Turbines [J].
Chen, Aikang ;
Xie, Da ;
Zhang, Daming ;
Gu, Chenghong ;
Wang, Keyou .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2019, 34 (07) :6345-6355
[6]   SSR Mitigation of Series-Compensated DFIG Wind Farms by a Nonlinear Damping Controller Using Partial Feedback Linearization [J].
Chowdhury, M. A. ;
Shafiullah, G. M. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2018, 33 (03) :2528-2538
[7]  
[高本锋 Gao Benfeng], 2019, [电网技术, Power System Technology], V43, P655
[8]  
Gao Benfeng, 2015, Electric Power Automation Equipment, V35, P11, DOI 10.16081/j.issn.1006-6047.2015.12.002
[9]   Modifying the control design of DFIG-based wind turbines in order to inhibit power system oscillations [J].
Jafarian, Mohammad ;
Asefi, Mohammad-Naser .
JOURNAL OF ENGINEERING-JOE, 2019, (18) :5330-5334
[10]   Integration of DFIG-Based Wind Farms Into Series-Compensated Transmission Systems [J].
Leon, Andres E. .