A coordination and optimization method for under frequency load shedding and pump shedding suiting frequency safety and stability

被引:0
作者
Li, Lin [1 ]
Zhou, Xia [1 ]
Luo, Jianbo [1 ]
Zhao, Juan [2 ]
Song, Jinhai [1 ]
Li, Wei [1 ]
机构
[1] State Grid Electric Power Research Institute
[2] Henan Power Operation and Communication Centre
来源
Dianli Xitong Zidonghua/Automation of Electric Power Systems | 2012年 / 36卷 / 13期
关键词
Coordination and optimization; Frequency security; Pump-storage; Under frequency load shedding (UFLS); Under frequency pump shedding (UFPS);
D O I
10.3969/j.issn.1000-1026.2012.13.005
中图分类号
学科分类号
摘要
Based on time domain simulation analysis method, through observing and comparing the trajectories, under frequency load shedding (UFLS) is compared with under frequency pump shedding (UFPS) in their performance and effectiveness. Then UFLS and UFPS scheme setting methods are proposed. The coordination and optimization method between UFLS and UFPS is firstly proposed. The proposed method is verified through case studies, and the results show that this method is effective and feasible. © 2012 State Grid Electric Power Research Institute Press.
引用
收藏
页码:26 / 31
页数:5
相关论文
共 20 条
  • [1] Chen J., Hong L., Zheng Z., Investigation and application of under-frequency load shedding, Relay, 35, 14, pp. 79-82, (2007)
  • [2] Hou Y., Ao X., Gu L., Research on the adaptability of conventional UFLS/UVLS criteria for interconnected power systems, Power System and Clean Energy, 25, 1, pp. 12-16, (2009)
  • [3] (2011)
  • [4] Zhou J., Advantages of Tianhuangping pumped-storage power station in emergency reserve, East China Electric Power, 37, 4, pp. 589-593, (2009)
  • [5] He Y., Guan L., Cai Q., Et al., Analysis of security function and economic benefit of pumped storage station in power grid, Power System Technology, 28, 20, pp. 54-58, (2004)
  • [6] Gao S., Lou S., Review on the evaluation of static and dynamic benefits of pumped storage power plants, Hydropower Automation and Dam Monitoring, 32, 1, pp. 11-15, (2008)
  • [7] Development of pumped storage power station in Qinghai, Power System and Clean Energy, 25, 9, pp. 62-64, (2009)
  • [8] Zhang D., Chen T., Li Y., Et al., Study on the functions of the pumped storage power stations in electric power grid in Japan, Electric Power Technology, 19, 1, pp. 15-19, (2010)
  • [9] Luo Y., Low frequency protection setting for pumped storage units, Hydropower Automation and Dam Monitoring, 35, 3, pp. 52-55, (2011)
  • [10] Xu T., Xue Y., Quantitative assessments of transient frequency deviation acceptability, Automation of Electric Power Systems, 26, 19, pp. 7-10, (2002)