An Approach for Electrical Harmonic Analysis Based on Optimized Composite Cosine Window Four-spectrum-line Interpolation FFT

被引:0
|
作者
Chen Z. [1 ]
Wang L. [1 ]
Wang C. [1 ]
Shen P. [1 ]
Li Z. [1 ]
机构
[1] School of Electrical Engineering, Beijing Jiaotong University, Haidian District, Beijing
来源
Dianwang Jishu/Power System Technology | 2020年 / 44卷 / 03期
关键词
FFT; Four-spectrum-line interpolation; Genetic algorithm; Harmonic analysis; Window function parameter optimization;
D O I
10.13335/j.1000-3673.pst.2019.0075
中图分类号
学科分类号
摘要
When fast Fourier transform (FFT) method is used to analyze power harmonics, non-synchronous sampling and non-integer periodic truncation of signal would cause spectral leakage and fence effect, leading to certain detection errors. Window functions and interpolation algorithms can effectively improve detection accuracy of the FFT method. The spectral characteristics of the window function directly affect improvement effect. Therefore, a window function parameter optimization method based on genetic algorithm (GA) is proposed. The combined cosine window function is optimized using this method. A six-term fifth-order cosine window function is obtained, and an approach for electrical harmonic analysis based on this window four-spectrum-line interpolation FFT is achieved. Simulation shows that the detection result is better than adding third-order Nuttall window and fifth-order Nuttall window. © 2020, Power System Technology Press. All right reserved.
引用
收藏
页码:1105 / 1113
页数:8
相关论文
共 19 条
  • [1] Yang F., Li X., Zheng X., The research of representative character and emergence mechanism and their harms for fraction-harmonics, High Voltage Engineering, 33, 12, pp. 153-156, (2007)
  • [2] Zhang F., Geng Z., Ge Y., FFT algorithm with high accuracy for harmonic analysis in power system, Proceedings of the CSEE, 19, 3, pp. 63-66, (1999)
  • [3] Chen M., Liu Y., Han X., Et al., Harmonic distribution modeling based on non-parametric estimation and harmonic prediction evaluation for high speed railway traction load, Power System Technology, 41, 8, pp. 2598-2603, (2017)
  • [4] Zhang L., Li J., Bi T., Et al., Subsynchronous and supersynchronous inter-harmonic identification method based on phasor measurements, Power System Technology, 41, 10, pp. 3237-3245, (2017)
  • [5] Zou P., Huang C., Jiang H., Et al., Method of harmonics and interharmonics measurement based on all-phase spectrum zoom and correction, Power System Technology, 40, 8, pp. 2496-2502, (2016)
  • [6] Zhang X., Luo R., Zhao W., Et al., Fast quasi-synchronous harmonic algorithm for IEC61850 based digital energy metering devices, Power System Technology, 42, 2, pp. 621-627, (2018)
  • [7] Li G., Chen Z., Ning Y., Two improved methods of fast Fourier transform, Automation of Electric Power Systems, 21, 12, pp. 37-40, (1997)
  • [8] Pan W., Qian Y., Zhou E., Power harmonies measurement based on windows and interpolated FFT(II) dual interpolated FFT algorithms, Transactions of China Electrotechnical Society, 9, 2, pp. 53-56, (1994)
  • [9] Qing B., Teng Z., Gao Y., Et al., An approach for electrical harmonic analysis based on Nuttall window double-spectrum-line interpolation FFT, Proceedings of the CSEE, 28, 25, pp. 153-158, (2008)
  • [10] Zhai R., Ying C., Ren G., Et al., An approach for harmonic analysis based on Nuttall window and triple-s pectral-line interpolation, Power System Protection and Control, 43, 10, pp. 38-43, (2015)