Control study of wind farm integrated to weak grid by VSC-HVDC

被引:0
|
作者
Bian, Xiaoyan [1 ]
Hong, Lijun [2 ]
Wang, Yi [3 ]
Hong, Jianshan [4 ]
Fu, Yang [1 ]
机构
[1] School of Electrical Engineering, Shanghai University of Electric Power, Shanghai,200090, China
[2] Jinhua Electric Power Supply Company, Jinhua,321000, China
[3] Shanghai Donghai Wind Power Co. Ltd., Shanghai,200090, China
[4] Zhejiang Power Grid Company, Hangzhou,310027, China
来源
关键词
Electric power system control - Integration - Power converters - Electric frequency control - Electric power transmission networks - Electric power system interconnection - Electric utilities - Asynchronous generators - Electric machine control - Electric fault currents - HVDC power transmission - Wind turbines;
D O I
暂无
中图分类号
学科分类号
摘要
The reactive and active power variation of grid- connected wind farms leads to voltage and frequency fluctuations and instability of power grid. The voltage and frequency control model of Voltage Source Converter HVDC (VSC- HVDC) was proposed to overcome this problem. The mathematical model of wind farm integration system was systematically built. The control link of VSC-HVDC converter WFVSC and GSVSC was well designed. The frequency link was also added to the traditional control model of voltage and power outer loop control and current inner loop control to solve the problem that double fed variable speed wind turbine could not response to frequency variation when the grid frequency changed. The test system of wind farm integration by VSC-HVDC to grid was established, the corresponding HVAC integration was applied for comparison, and wind speed fluctuations and fault were simulated. The simulation results verify that the proposed control model of VSC-HVDC is correct and valid based on test system.
引用
收藏
页码:1355 / 1362
相关论文
共 50 条
  • [1] Study on Stability Improvement of Wind Farm Integrated to Weak Grid by VSC-HVDC
    Bian, Xiao-Yan
    Hong, Li-Jun
    Fu, Yang
    ENERGY DEVELOPMENT, PTS 1-4, 2014, 860-863 : 267 - +
  • [2] The Study of Control Strategy for VSC-HVDC applied in offshore wind farm and grid connection
    Dong, Huang
    Yuan, Mao
    2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
  • [3] Fault Location in VSC-HVDC section for Grid Integrated Offshore Wind Farm by EMD
    Perveen, Rehana
    Mohanty, Soumya R.
    Kishor, Nand
    PROCEEDINGS OF THE 18TH MEDITERRANEAN ELECTROTECHNICAL CONFERENCE MELECON 2016, 2016,
  • [4] Mitigation of subsynchronous oscillation in a VSC-HVDC connected offshore wind farm integrated to grid
    Zhou, Qibin
    Ding, Yang
    Mai, Kun
    Bian, Xiaoyan
    Zhou, Bo
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 109 : 29 - 37
  • [5] Fault Ride-Through Control of the Wind Farm Integrated with VSC-HVDC
    Wang, Yi
    Su, Xiaoqing
    Han, Xiao
    2013 INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS), 2013, : 267 - 272
  • [6] A novel control method for a VSC-HVDC system in a grid-connected wind farm
    Liu, Yingpei
    Li, Ran
    TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES, 2015, 23 (06) : 1558 - 1570
  • [7] Optimal Coordination of Overcurrent Relay for Offshore Wind Farm Integrated to Onshore Grid with VSC-HVDC
    Perveen, Rehana
    Mohanty, Soumya R.
    Kishor, Nand
    2014 6TH IEEE POWER INDIA INTERNATIONAL CONFERENCE (PIICON), 2014,
  • [9] Integration of Wind Farm to VSC-HVDC System
    Jose, Subin
    Geetha, R. S.
    2017 INTERNATIONAL CONFERENCE ON SMART GRIDS, POWER AND ADVANCED CONTROL ENGINEERING (ICSPACE), 2017, : 298 - 302
  • [10] Study on VSC-HVDC grid topology of offshore wind farms
    Nguyen Thi Hong Yen
    Chen Hongkun
    Le Ngoc Giang
    Cluster Computing, 2019, 22 : 14803 - 14810