Control method for APF hysteresis-band current tracking based on digital over-sampling

被引:0
作者
Cao, Wu [1 ]
Liu, Kangli [1 ]
Jiang, Nan [1 ]
Zhao, Jianfeng [1 ]
机构
[1] School of Electrical Engineering, Southeast University
来源
Dianli Xitong Zidonghua/Automation of Electric Power Systems | 2014年 / 38卷 / 06期
关键词
Active power filter (APF); Digital implementation; Digital processor; Hysteresis-band current control; Over-sampling;
D O I
10.7500/AEPS20130613013
中图分类号
学科分类号
摘要
An implementation method for hysteresis-band current tracking for active power filter (APF) based on digital over-sampling is proposed, which enables precise compensation of harmonic current and stabilizes the switching-frequency. This method can meet different dynamic response demands of control and operation modules by utilizing different extraction factors of digital chip over-sampling. And it fully coordinates two kinds of operations in the digital signal processor (DSP), the sampling interrupt operation and main loop operation, which ensures real-time harmonic current detection and synchronous tracking for the compensating current. The same reference will be tracked N times and the change of power switching device status depends only on the parameters of the preceding switching-period, resulting in high precision tracking for current. Compared with the traditional hysteresis-band current control method, the proposed method has the advantage of not only stabilized switching-frequency but precise harmonic compensation as well, proving its applicability and reliability. A 65 kVA experiment system for three-phase three-wire APF is built for verification and the validity of the proposed method is confirmed by experimental results. © 2014 State Grid Electric Power Research Institute Press.
引用
收藏
页码:85 / 90
页数:5
相关论文
共 15 条
[1]  
Buso S., Fasolo S., Malesani L., Et al., A dead-beat adaptive hysteresis current control, IEEE Trans on Industry Applications, 36, 4, pp. 1174-1180, (2000)
[2]  
Fan X., Zhang D., Sun Q., Et al., Hysteresis current control strategy for three-phase three-wire active power filter, Automation of Electric Power Systems, 31, 18, pp. 57-60, (2007)
[3]  
Shen Z., Zheng J., Mei J., Et al., Double hysteresis current tracking control scheme for active power filter based on improved voltage space vector, Proceedings of the CSEE, 31, 15, pp. 8-14, (2011)
[4]  
Zhang X., Wang Z., A new method based on over-sampling technique to improve sampling precision, Automation of Electric Power Systems, 28, 14, pp. 58-62, (2004)
[5]  
Zhao Y., Sun L., Tan N., An integrated circuit oriented harmonics measurement algorithm based on non-uniform synchronized oversampling, Automation of Electric Power Systems, 37, 7, pp. 102-106, (2013)
[6]  
Tekwani P.N., Kanchan R.S., Gopakumar K., Novel current error space phasor based hysteresis controller using parabolic bands for control of switching frequency variations, IEEE Trans on Industrial Electronics, 54, 5, pp. 2648-2656, (2007)
[7]  
Malesani L., Mattavelli P., Tomasin P., Improved constant-frequency hysteresis current control of VSI inverters with simple feedforward bandwidth prediction, IEEE Trans on Industry Applications, 33, 5, pp. 1194-1202, (1997)
[8]  
Yang X., Wang Z., A novel quasi-constant hysteretic PWM current mode control approach, Transactions of China Electrotechnical Society, 18, 3, pp. 24-28, (2003)
[9]  
Hong F., Shan R., Wang H., Et al., A varied hysteresis-band current controller with fixed switching frequency, Transactions of China Electrotechnical Society, 24, 1, pp. 115-119, (2009)
[10]  
Mohseni M., Islam S.M., A new vector-based hysteresis current control scheme for three-phase PWM voltage-source inverters, IEEE Trans on Power Electronics, 25, 9, pp. 2299-2309, (2010)