Wind-resistant reliability analysis of UHV transmission tower based on moment methods

被引:0
|
作者
机构
[1] School of Civil Engineering, Chongqing University
[2] Key Laboratory of New Technology for Construction of Cities in Mountain Area (Chongqing University), Ministry of Education
来源
Yu, D.-K. (yudengkevip@126.com) | 1600年 / Tsinghua University卷 / 30期
关键词
Equivalent extreme-value event; Moment method; Random equivalent static wind load; System reliability; UHV transmission tower;
D O I
10.6052/j.issn.1000-4750.2011.11.0803
中图分类号
学科分类号
摘要
This paper analyzes the wind-resistant reliability of UHV transmission tower. A moment method based on the equivalent extreme-value event is introduced to study the system reliability of UHV transmission tower under a random equivalent static wind load. By using point estimate methods for probability moments, the reliability index and the failure probability are obtained through this moment method. A numerical example of 1000kV UHV transmission tower indicates that: 1) being very simple and effective, the moment method can be applied to UHV transmission tower reliability analysis and is of great significance and practical engineering value; 2) the number of estimating points based on the point estimate methods for probability moments should depend on the convergence of failure probability, which means that it is not reasonable to choose freely or to attain the more the better.
引用
收藏
页码:311 / 316
页数:5
相关论文
共 23 条
  • [1] Zhang X., Structural Wind Engineering, pp. 300-327, (2006)
  • [2] Deoliya R., Datta T.K., Reliability analysis of a microwave tower for fluctuating mean wind with directional effect, Reliability Engineering and System Safety, 67, 2000, pp. 257-267, (1999)
  • [3] Xie Q., Li J., Current situation of natural disaster in electric power system and counter measures, Journal of Natural Disasters, 15, 4, pp. 126-131, (2006)
  • [4] GB 50068-2001, Unified standard for reliability design of building structures, (2001)
  • [5] GB 50009-2001, Load code for the design of building structures, (2001)
  • [6] DL/T 5092-1999, Technical code for designing 110~500kV overhead transmission line, (1999)
  • [7] DL/T 5154-2002, Technical regulation of design for tower and pole structures of overhead transmission line, (2002)
  • [8] Ou J., Duan Y., A random equivalent static wind load for wind-resistant reliability analysis and design of structures, Journal of Building Structures, 16, 7, pp. 27-33, (1995)
  • [9] Ou J., Duan Y., Ye J., A random equivalent static wind load model and its parameter determination, Journal of Harbin Architecture and Civil Engineering Institute, 27, 2, pp. 1-8, (1994)
  • [10] Visweswara Rao G., Optimum designs for transmission line tower, Computers & Structures, 57, 1, pp. 81-93, (1995)