Discrete-Time Domain Current Control Strategy for High Power Grid-Connected Converters

被引:0
|
作者
Wang X. [1 ]
Yang S. [1 ]
Li D. [1 ]
Zhang X. [1 ]
机构
[1] National and Local Joint Engineering Laboratory for Renewable Energy Access to Grid Technology, Hefei University of Technology, Hefei
来源
Diangong Jishu Xuebao/Transactions of China Electrotechnical Society | 2024年 / 39卷 / 08期
关键词
discrete-time control; grid harmonics; Grid-connected converter with LCL; low switching frequency;
D O I
10.19595/j.cnki.1000-6753.tces.222309
中图分类号
学科分类号
摘要
For high-power grid-connected converters, the switching frequency usually is low. Consequently, the adverse effects enforced by the control delay and discretizing errors are heavy. However, traditional current control strategies generally ignore these effects, reducing the performance of the designed controller. Recently, some strategies were presented to compensate for the control delay and the discretizing errors. However, most suffer from low dynamic response and high sensitivity to the power grid harmonics. Therefore, a current control strategy combining the bridge arm-side and the grid-side currents is designed directly in the discrete-time domain, and pole-zero placement is used in synchronous coordinates. Meanwhile, a differentiator to the capacitor voltage is introduced to estimate the grid-side currents. Consequently, hardware complexity and the corresponding control cost are reduced. The discrete-time model of the converter with LCL is built in synchronous coordinates as the output filter, including the computational delay, firstly. The corresponding structure of the combined state-space control scheme is as follows: the harmonic control loop of the grid-side currents is constructed and combined with the fundamental current control loop on the bridge arm-side using the full state-feedback control. And then, the integral controller is introduced for improved disturbance rejection, and the reference-feedforward controller is designed to increase the reference-tracking dynamic performance. Consequently, the closed-loop transfer function of the system is obtained based on the discrete-time model and the control scheme. Then the state feedback function matrix and the feedforward module are optimized based on the pole-zero placement. Finally, a differentiator is introduced to estimate the grid-side currents, reducing the hardware cost. Experiment results based on a hardware-in-loop simulator show that the response time of the bridge arm-side currents to a 1 000 A step-up change is about 4.5 ms; the recovery time of the bridge arm-side currents facing a grid-voltage dip of 0.4(pu) is about 10ms; and the total harmonic distortion of the grid-side currents is 2.28%, below the 5% limit given in standards, in the circumstances of 6% fifth and seventh harmonic components appearing in the grid voltage. Finally, to verify the robustness of the proposed strategy to the parameter deviations, the actual system parameters are deviated artificially from their nominal values. The results show that the proposed strategy can operate satisfactorily in the range of ±40% parameter deviations, and the influence of the parameter deviations is low. The following conclusions can be drawn from the experiment results: (1) Compared with the typical discrete-time state-space control strategy, the proposed strategy keeps the same dynamic performance while improving the capability of rejecting the grid harmonic disturbance. (2) The proposed control strategy simplifies the design complexity based on the direct pole-zero placement and increases freedom degrees by combining the design of fundamental current and harmonic control loops. (3) The differentiator to the capacitor voltage is designed to acquire grid-side currents without additional current sensors and the corresponding sampling circuit, reducing the hardware complexity and the cost. © 2024 China Machine Press. All rights reserved.
引用
收藏
页码:2523 / 2540
页数:17
相关论文
共 28 条
  • [1] Sharma H R, Suryawanshi H M, Chaturvedi P, Et al., Implementation of passive damping technique in LCL filter for three-phase grid connected inverter, 2022 IEEE 2nd International Conference on Sustainable Energy and Future Electric Transportation (SeFeT), pp. 1-6, (2022)
  • [2] Li Xiaoqiang, Wu Xiaojie, Geng Yiwen, Et al., Wide damping region for LCL-type grid-connected inverter with an improved capacitor-current-feedback method, IEEE Transactions on Power Electronics, 30, 9, pp. 5247-5259, (2015)
  • [3] Xin Zhen, Loh P C, Wang Xiongfei, Et al., Highly accurate derivatives for LCL-filtered grid converter with capacitor voltage active damping, IEEE Transactions on Power Electronics, 31, 5, pp. 3612-3625, (2016)
  • [4] Pan Donghua, Ruan Xinbo, Wang Xuehua, Direct realization of digital differentiators in discrete domain for active damping of LCL-type grid-connected inverter, IEEE Transactions on Power Electronic, 33, 10, pp. 8461-8473, (2018)
  • [5] Chen Chen, Xiong Jian, Wan Zhiqiang, Et al., A time delay compensation method based on area equivalence for active damping of an LCL-type converter, IEEE Transactions on Power Electronics, 32, 1, pp. 762-772, (2017)
  • [6] Fang Tianzhi, Huang Chun, Chen Naiming, Et al., A phase-lead compensation strategy on enhancing robustness of LCL-type grid-tied inverters under weak grid conditions, Transactions of China Electrotechnical Society, 33, 20, pp. 4813-4822, (2018)
  • [7] Zhang Sen, Zhao Jianfeng, Liu Kangli, Et al., Research on the impacts of digital control delay on the effectiveness of current loop decoupling, Transactions of China Electrotechnical Society, 35, S2, pp. 484-493, (2020)
  • [8] Dannehl J, Liserre M, Fuchs F W., Filter-based active damping of voltage source converters with LCL filter, IEEE Transactions on Industrial Electronics, 58, 8, pp. 3623-3633, (2011)
  • [9] Nussbaumer T, Heldwein M L, Gong Guanghai, Et al., Comparison of prediction techniques to compensate time delays caused by digital control of a three-phase Buck-type PWM rectifier system, IEEE Transactions on Industrial Electronics, 55, 2, pp. 791-799, (2008)
  • [10] Corradini L, Stefanutti W, Mattavelli P., Analysis of multi-sampled current control for active filters, 2007 IEEE Industry Applications Annual Meeting, pp. 1608-1615, (2007)