Current dividing process of paralleled circuit breakers with high coupled split reactor

被引:7
作者
Yuan, Zhao [1 ]
Yin, Xiaogen [1 ]
Pan, Yuan [1 ]
He, Junjia [1 ]
机构
[1] State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology
来源
Gaodianya Jishu/High Voltage Engineering | 2012年 / 38卷 / 08期
关键词
Arc resistance; Coupling coefficient; Current dividing; Current limiting reactor; High coupled split reactor; Paralleled circuit breakers;
D O I
10.3969/j.issn.1003-6520.2012.08.027
中图分类号
学科分类号
摘要
Focussing on the current sharing process of the paralleled circuit breakers with a high coupled split reactor (HCSR), we put forward the expressions of imbalance current of simply paralleled circuit breakers and the paralleled circuit breakers with HCSR. Conclusions could be drawn that the current limiting reactor and coupling coefficient of HCSR and the arc resistance of the circuit breakers were main factors that affected the current sharing results. In order to prove the onclusions above, the simulation models of HCSR and vacuum/SF 6 circuit breakers were established to simulate the current sharing of paralleled circuit breakers, and a synthetic circuit test of paralleled circuit breakers was also conducted. The simulation and test results are consistent with the analysis conclusions. The research results give a principle to choose the parameters of HCSR under different types of circuit breakers, and can be used to guide the design of paralleled circuit breakers with HCSR.
引用
收藏
页码:2008 / 2014
页数:6
相关论文
共 24 条
[1]  
Lu J., Zhao C., Fang Z., Et al., Simulation and experiment of a novel fault current limiter, High Voltage Engineering, 36, 9, pp. 2258-2264, (2010)
[2]  
Bai H., Li G., Discussion on weak open-loop mode of electromagnetic loop, Power System Protection and Control, 38, 2, pp. 60-63, (2010)
[3]  
Han G., Han L., Wu L., Application and development of methods on limiting power grid s short-circuit current, Power System Protection and Control, 38, 1, pp. 141-144, (2010)
[4]  
Sun Q., Cai Z., Li A., Et al., A Short-circuit current over-limited mechanism of 500 kV power system and the adaptability of limiting measures, Automation of Electric Power Systems, 33, 21, pp. 92-96, (2009)
[5]  
Chen H., Yang L., Yang G., Et al., Application of fault current limiter on EHV grid, East China Electric Power, 39, 1, pp. 36-39, (2011)
[6]  
Hu R., Chao Q., Chang X., Et al., Analysis of 220 kV short-circuit current of xinjiang power grid and research of restrictive measures, Sichuan Electric Power Technology, 34, 3, pp. 19-21, (2011)
[7]  
Cai G., Cao H., Study on the short-circuit current limiting measures in guangdong power grid, Southern Power System Technology, 5, 1, pp. 90-94, (2011)
[8]  
Zhang D., Liu D., Cheng C., Application of superconductive current limiter to power grids, Transformer, 48, 6, pp. 20-22, (2011)
[9]  
Pertsev A.A., Belkin G.S., Rylskeya L.A., Et al., Parallel connection of several vacuum interrupters in a circuit-breaker pole, Proceeding of 19th ISDEIV, pp. 407-410, (2000)
[10]  
Pertsev A.A., Chistjakov S.P., Rylskeya L.A., Et al., Parallel connection of several vacuum interrupters in a circuit-breaker pole, Proceeding of 21st ISDEIV, pp. 333-336, (2004)