Security evaluation for UHV synchronized power grid

被引:0
|
作者
Tang Y. [1 ]
Guo Q. [1 ]
Zhou Q. [1 ]
Qin Q. [1 ]
Qin X. [1 ]
机构
[1] China Electric Power Research Institute, Haidian District, Beijing
来源
关键词
Security and stability; Synchronized power grids; Three-defense lines; UHV;
D O I
10.13335/j.1000-3673.pst.2016.01.014
中图分类号
学科分类号
摘要
According to 'Guide on Security and Stability for Power System', security and stability of UHV synchronized power grids were evaluated in following aspects: short-circuit current, static security, transient and dynamic stabilities. Based on requirements of 'Emergency disposal, investigation and settlement regulations of electrical safety incidents', fault tolerance ability of UHV power grids and available measures were verified under serious failure conditions, probably caused by natural disasters. According to setting principles and requirements, adaptability of the third defense line was analyzed including under-frequency load shedding, under-voltage load shedding and splitting. Results indicated that security performance of UHV synchronized power grids can meet demands of 'Guide on Security and Stability for Power System' and has strong capability of withstanding serious failure. The third defense line can effectively control failurescope and avoid blackouts. Self-adaptive splitting technique based on wide area synchronous measurement information, together with AC-DC coordinated control technique, can further improve power gridsecurity performance. © 2016, Power System Technology Press. All right reserved.
引用
收藏
页码:97 / 104
页数:7
相关论文
共 15 条
  • [1] Bai J., Yan X., Cheng L., Research on power flow and power source installation planning scheme during the 13th Five-Year period, Electric Power, 48, 1, pp. 15-20, (2015)
  • [2] Qin Q., Guo Q., Zhou Q., Et al., The security and stability of power grids in 13th Five-Year planning and countermeasures, Electric Power, 48, 1, pp. 25-32, (2015)
  • [3] Liu N., Tang X., Zhang W., Et al., Study on electromagnetic ring opening in Henan province under ultra-high voltage power grid, Power System Protection and Control, 39, 2, pp. 131-136, (2011)
  • [4] Yao Y., Miao Y., Chen H., Et al., Research on electromagnetic looped network after Huainan-Shanghai UHV AC transmission system was put into operation, East China Electric Power, 42, 1, pp. 30-32, (2014)
  • [5] Zhao Q., Liu Z., Zhang L., Discussions on the several problems of under-frequency load shedding scheme in China, Automation of Electric Power Systems, 34, 11, pp. 48-53, (2010)
  • [6] Ma S., Yi J., Sun H., Et al., Study on configuration of under-voltage load shedding in power systems, Automation of Electric Power Systems, 33, 5, pp. 45-49, (2009)
  • [7] Fang Y., Adaptive islanding control of power systems, Automation of Electric Power Systems, 31, 20, pp. 41-44, (2007)
  • [8] Senroy N., Heydt G.T., A conceptual framework for the controlled islanding of interconnected power systems, IEEE Transactions on Power Systems, 21, 2, pp. 1005-1006, (2006)
  • [9] Xu W., Dai S., Zhang Q., Et al., Comments and overviews on the islanding methods of large interconnected power grid, Proceedings of the CSEE, 35, 11, pp. 2756-2769, (2015)
  • [10] Qin X., Ma S., Tang X., Et al., Study on power system out-of-step criterion based on WAMS, IEEE Power Engineering Society General Meeting, pp. 1-5, (2011)