Experimental performance investigation on a desiccant-assisted two-stage evaporative cooling system in hot and humid areas

被引:8
作者
Zhang, Yanling [1 ,2 ]
Chen, Yi [3 ]
Yang, Hongxing [1 ]
Zhang, Hao [2 ]
Leung, Chun Wah [2 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Environm & Energy Engn, Renewable Energy Res Grp, Hong Kong, Peoples R China
[2] Hong Kong Polytech Univ, Sch Profess Educ & Execut Dev, Hong Kong, Peoples R China
[3] Jimei Univ, Coll Marine Equipment & Mech Engn, Xiamen, Peoples R China
关键词
Desiccant-enhanced evaporative cooling; Two-stage indirect evaporative cooling; Air conditioning; Performance optimization; Eco-friendly air handling; DEHUMIDIFICATION; CHINA;
D O I
10.1016/j.apenergy.2024.124704
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The escalating demand for energy-efficient and eco-friendly air conditioning systems in buildings has spurred the development of comfortable, efficient, and cost-effective air handling system configurations. Desiccant cooling has shown a higher coefficient of performance (COP) compared to traditional vapor compression refrigeration (MVCR) systems. However, current desiccant cooling facilities struggle to decouple and efficiently handle indoor heat and moisture loads. The complexity of these facilities has kept intricate cooling systems remaining theoretical, requiring simplification and experimental investigation. This paper presents an experimental study on a compact, two-stage evaporative cooling system assisted by a liquid desiccant. A key innovation of this system is the inclusion of a two-stage heat exchanger that adeptly manages the decoupling of indoor heat and moisture loads under challenging high-temperature and high-humidity conditions. Performance analysis was conducted experimentally under three hot and humid climatic conditions using an optimized operating parameter scheme. Starting from an initial condition of 36.22 degrees C and a humidity ratio of 0.028 kg/kg, the proposed system achieves COP values ranging from 11.3 to 18.4 without compromising indoor comfort or facility compactness. Under high heat and high humidity conditions, the optimized system extracts 20 % of the product air as the secondary air source. It can reach a minimum supply air temperature of 18.44 degrees C, achieved under optimized conditions of low wind speed (1.0 m/s), high desiccant concentration (35 %), and substantial desiccant flow (0.09 kg/s). Experimental studies of this new system provide the possibility of achieving high efficiency in air handling over a wide range of temperatures and humidity.
引用
收藏
页数:16
相关论文
共 52 条
[1]   A review of desiccant evaporative cooling systems in hot and humid climates [J].
Abd Manaf, Ismanizam ;
Durrani, Faisal ;
Eftekhari, Mahroo .
ADVANCES IN BUILDING ENERGY RESEARCH, 2021, 15 (01) :1-42
[2]   Technological development of evaporative cooling systems and its integration with air dehumidification processes: A review [J].
Abdullah, Shekh ;
Zubir, Mohd Nashrul Bin Mohd ;
Bin Muhamad, Mohd Ridha ;
Newaz, Kazi Md Salim ;
Oztop, Hakan F. ;
Alam, Md Shadab ;
Shaikh, Kaleemullah .
ENERGY AND BUILDINGS, 2023, 283
[3]   Experimental evaluation of one, two, and three stage evaporative cooling systems [J].
Al-Juwayhel, F ;
El-Dessouky, H ;
Ettouney, H ;
Al-Qattan, M .
HEAT TRANSFER ENGINEERING, 2004, 25 (06) :72-86
[4]  
Ashrae, 2005, ASHRAE handbook: fundamentals
[5]   Parametric analysis of a combined dew point evaporative-vapour compression based air conditioning system [J].
Chauhan, Shailendra Singh ;
Rajput, S. P. S. .
ALEXANDRIA ENGINEERING JOURNAL, 2016, 55 (03) :2333-2344
[6]   Investigation on solar assisted liquid desiccant dehumidifier and evaporative cooling system for fresh air treatment [J].
Chen, Yi ;
Yang, Hongxing ;
Luo, Yimo .
ENERGY, 2018, 143 :114-127
[7]   Comfortable air speeds for young people lying at rest in the hot-humid area of China in summer [J].
Chen, Yi ;
Zhang, Yufeng ;
Tang, Haolei .
BUILDING AND ENVIRONMENT, 2017, 124 :402-411
[8]   Review of solar regeneration methods for liquid desiccant air-conditioning system [J].
Cheng, Qing ;
Zhang, Xiaosong .
ENERGY AND BUILDINGS, 2013, 67 :426-433
[9]   Evaluation of thermal comfort in an office building served by a liquid desiccant-assisted evaporative cooling air-conditioning system [J].
Cho, Hye-Jin ;
Jeong, Jae-Weon .
ENERGY AND BUILDINGS, 2018, 172 :361-370
[10]   Experimental research on the cooling performance of a new regenerative dew point indirect evaporative cooler [J].
Chu, Junjie ;
Xu, Wei ;
Fu, Yijun ;
Huo, Huimin .
JOURNAL OF BUILDING ENGINEERING, 2021, 43