A novel pilot protection scheme for HVDC transmission line based on current waveform matching

被引:0
|
作者
Liu, Jian [1 ]
Tai, Nengling [1 ]
Fan, Chunju [1 ]
机构
[1] School of Electronic Information and Electrical Engineering, Shanghai Jiaotong University, Minhang District,, Shanghai
来源
Dianwang Jishu/Power System Technology | 2015年 / 39卷 / 06期
基金
中国国家自然科学基金;
关键词
DC-filter; HVDC transmission line; Impedance characteristic; Pilot protection; Waveform matching;
D O I
10.13335/j.1000-3673.pst.2015.06.043
中图分类号
学科分类号
摘要
In this paper a novel pilot protection principle for HVDC transmission lines is proposed based onwaveform characteristics analysis of specific current at both terminals of DC line. The impedance value of DC-filter at specific frequency is found nearly zero with spectrum analysis. Namely, there is no specific frequency current detected by DC shunts during normal operation, while the current will increase significantly when fault occurs due to system impedance change. Equivalent network for DC system at specific frequency is analyzed and it is found that when internal faults occur, the direction of specific current detected at DC line ends is from DC bus to DC line, while the direction of specific current detected at rectifier side is from DC line to DC bus and direction of specific current detected at inverter side is from DC bus to DC line during external faults at rectifier side. The situation of external fault at inverter side is opposite to that of faults at inverter side. The direction difference of specific current at DC line ends leads to significant difference in waveform matching, which can be used to identify the fault location(external or internal). An improved backup protection scheme for HVDC transmission line is also proposed to overcome the shortage of the existing current differential protection. Simulation results show that the proposed protection scheme can identify internal and external faults reliably, and owns ability to respond to faults with high transition resistance. ©, 2015, Power System Technology Press. All right reserved.
引用
收藏
页码:1736 / 1743
页数:7
相关论文
共 17 条
  • [1] Kang L., Tang K., Luo J., Et al., Two-terminal fault location of monopolar earth fault in HVDC transmission line, Power System Technology, 38, 8, pp. 2268-2273, (2014)
  • [2] Liu H., Xu Z., Jin L., A review of the reliability survey of long distance high power HVDC transmission project throughout the world, High Voltage Engineering, 38, 3, pp. 1-4, (2002)
  • [3] Han K., Cai Z., Xu M., Et al., Dynamic characteristics of characteristic parameters of traveling wave protection for HVDC transmission line and their setting, Power System Technology, 37, 1, pp. 255-260, (2013)
  • [4] Song G., Gao S., Cai X., Et al., Survey of relay protection technology for HVDC transmission lines, Automation of Electric Power Systems, 36, 22, pp. 1-7, (2012)
  • [5] Liu K., Shu H., Yu J., Et al., Transient identification of lightning strokes on ±800 kV UHVDC transmission lines, Power System Technology, 37, 11, pp. 3007-3014, (2013)
  • [6] Liu X., Osman A.H., Hybrid traveling wave/boundary protection for monopolar HVDC line, IEEE Transactions on Power Delivery, 24, 2, pp. 569-578, (2009)
  • [7] Zhang Y., Tai N., Xu B., Travelling wave based pilot directional protection for HVDC line, Automation of Electric Power Systems, 36, 21, pp. 77-80, (2012)
  • [8] Ha H., Yu Y., Yi R., Et al., Novel scheme of travelling wave based differential protection for bipolar HVDC transmission lines, International Conference on Power System Technology, pp. 1-6, (2010)
  • [9] Zheng X., Tai N., Yang G., Et al., A transient protection scheme for HVDC transmission line, IEEE Transactions on Power Delivery, 27, 2, pp. 718-724, (2012)
  • [10] Takea H., Ayakawa H., Tsumenaga M., New protection method for HVDC lines including cables, IEEE Transactions on Power Delivery, 10, 4, pp. 2035-2037, (1995)