Application of the control methods for radiant floor cooling system in residential buildings

被引:85
作者
Department of Architecture, College of Engineering, Seoul National University, Seoul, Korea, Republic of [1 ]
不详 [2 ]
不详 [3 ]
机构
[1] Department of Architecture, College of Engineering, Seoul National University, Seoul
[2] Department of Architectural Engineering, College of Engineering, Kunsan National University, Kunsan
[3] Department of Architecture, College of Engineering, Seoul National University, Kwanak-gu 151-742 Seoul
来源
Build. Environ. | 2006年 / 1卷 / 60-73期
关键词
Comfort; Condensation; Control methods; Radiant floor cooling system (RFCS); Water flow control; Water temperature control;
D O I
10.1016/j.buildenv.2005.01.019
中图分类号
学科分类号
摘要
In applying radiant floor cooling, its control system must prevent the floor surface condensation in hot and humid weather conditions. With no additional dehumidification system, only the radiant floor cooling system prevents floor condensation. In this case, the effects of the control of the cooling system on the indoor conditions can be changed because of the thermal inertia of the systems. Also different types of control system can be composed according to the control methods, which can affect the construction cost in the design stage. Therefore, the control methods for the radiant cooling system with respect to floor surface condensation must be studied. Furthermore, because Korean people's lifestyle involves sitting on the floor, it is necessary to evaluate if a floor cooling system will influence the thermal comfort of the occupants. This study intends to clarify the control methods of the radiant floor cooling system and to analyze the control performance and applicability of each control method with regard to the floor surface condensation and comfort by computer simulations and experiments on the control methods of the radiant floor cooling system. The results of computer simulations and experiments show that water temperature control is better than water flow control with respect to temperature fluctuations in controlling room air temperature. To prevent floor surface condensation, the supply water temperature could be manipulated according to the dew point temperature in the most humid room, and in individual rooms, the water flow rate (on/off control) can be controlled. Also, the results of radiant cooling experiments show that the floor surface temperature remained above 21 °C, the temperature difference among surfaces remained below 6 °C, and the vertical air temperature difference remained below 1.9 °C, conforming well to comfort standards. © 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:60 / 73
页数:13
相关论文
共 41 条
[31]  
Diamond R.C., Feustel H.E., Dickerhoff D.J., Ventilation and infiltration in high-rise apartment buildings, (1996)
[32]  
Olesen B.W., Guidelines for comfort ASHRAE, Journal, pp. 40-45, (2000)
[33]  
Moderate thermal environments - Determination of the PMV and PPD indices and specification of the conditions for thermal comfort, (1994)
[34]  
Olesen B.W., Parsons K.C., Introduction to thermal comfort standards and to the proposed new version of EN ISO 7730, Energy and Buildings, 34, pp. 537-548, (2002)
[35]  
De Carli M., Olesen B.W., Field measurements of thermal comfort conditions in buildings with radiant surface cooling systems, (2001)
[36]  
Fanger P.O., Thermal comfort, (1970)
[37]  
Song G.-S., Jeon B.-K., Lee H.-W., A study on the comfort comparison between wooden floor and concrete floor based on seating life style, Journal of Architectural Institute of Korea, 16, 2, pp. 105-116, (2000)
[38]  
Song G.-S., Jeon B.-K., Kim K.-H., Jeon S.-W., A study on the comfort comparison based on thermal characteristics of the floor materials-steel, urethane rubber, fine tree, clay at the seating life style, Journal of Architectural Institute of Korea, 17, 2, pp. 207-216, (2001)
[39]  
Lee J.-Y., Isoda N., Mitsuda M., The effects of water cooled floor on thermal comfort of the human body, Journal of the Society of Living Environmental System in Korea, 7, 2, pp. 0-26, (2000)
[40]  
Olesen B.W., Possibilities and limitations of radiant floor cooling, ASHRAE Transactions, 103, 1, pp. 42-48, (1997)