Experimental investigation on the malfunction characteristics of the two-phase ejector in a typical enhanced refrigeration system

被引:2
作者
Bai, Tao [1 ]
Lu, Yu [2 ]
Wan, Jiahao [1 ]
Yu, Jianlin [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Dept Refrigerat & Cryogen Engn, Xian 710049, Peoples R China
[2] TBEA Xian Elect Technol Co Ltd, Xian 710099, Peoples R China
关键词
Experimental investigation; Malfunction; Two-phase Ejector; Structural parameters; Operating conditions; PERFORMANCE;
D O I
10.1016/j.applthermaleng.2024.125204
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, experimental research was conducted to explore ejector malfunctions caused by varying structural and operating parameters in the ejector outlet split ejector refrigeration system. Effective methods and strategies to mitigate ejector failure were proposed. The results indicated that inappropriate structural parameters led to ejector failure or instability. A smaller nozzle throat diameter and excessively large or small NXP values caused entrainment malfunction but not obvious pressure lift malfunctions. Conversely, a smaller mixing section diameter resulted in pressure lift malfunctions. The effect of the operating parameters on mass entrainment failures or instability was discussed. Smaller electronic expansion valve openings led to significant mass entrainment issues, and the ejector's instability became more pronounced with higher evaporator heat loads. The sensitivity of the electronic expansion valve opening to causing ejector malfunctions varied with different nozzle throat diameters. Throat diameters of 0.7 mm and 0.9 mm corresponded to TOP values of 10 % and 5 % for ejector failure, respectively. Strategies to address ejector entrainment malfunction or instability were studied. Increasing the electronic expansion valve opening effectively suppressed ejector failure, while merely adjusting compressor speed did not. A combined approach of increasing compressor speed and electronic expansion valve opening quickly resolved ejector malfunctions.
引用
收藏
页数:10
相关论文
共 23 条
[1]   Experimental investigation of a novel variable geometry radial ejector [J].
Al-Rbaihat, Raed ;
Saleh, Khalid ;
Malpress, Ray ;
Buttsworth, David .
APPLIED THERMAL ENGINEERING, 2023, 233
[2]   Influence of internal heat exchanger position on the performance of ejector-enhanced auto-cascade refrigeration cycle for the low-temperature freezer [J].
Bai, Tao ;
Yan, Gang ;
Yu, Jianlin .
ENERGY, 2022, 238
[3]   Experimental investigation on the dynamic malfunction behavior of the two-phase ejector in a modified auto-cascade freezer refrigeration system [J].
Bai, Tao ;
Yan, Gang ;
Yu, Jianlin .
ENERGY CONVERSION AND MANAGEMENT, 2019, 183 :382-390
[4]   Experimental investigation of an ejector-enhanced auto-cascade refrigeration system [J].
Bai, Tao ;
Yan, Gang ;
Yu, Jianlin .
APPLIED THERMAL ENGINEERING, 2018, 129 :792-801
[5]   Effect of spindle position on the performance and two-phase characteristics of controllable ejector for transcritical CO2 refrigeration system [J].
Chandran, R. Jishnu ;
Arumugam, Senthil Kumar ;
Sadasivan, Sreeja ;
John, Bibin ;
Kanna, P. Rajesh .
JOURNAL OF SUPERCRITICAL FLUIDS, 2024, 205
[6]   Experimental investigation on the dynamic characteristic of the direct expansion solar assisted ejector-compression heat pump cycle for water heater [J].
Chen, Jiaheng ;
Zhang, Guojie ;
Wang, Dingbiao .
APPLIED THERMAL ENGINEERING, 2021, 195
[7]  
Dupont J.L., 2019, ROLE REFRIGERATION G, DOI [10.18462/iif.NItec38.06.2019, DOI 10.18462/IIF.NITEC38.06.2019]
[8]   An experimental study of an ejector-boosted transcritical R744 refrigeration system including an exergy analysis [J].
Elbarghthi, Anas F. A. ;
Hafner, Armin ;
Banasiak, Krzysztof ;
Dvorak, Vaclav .
ENERGY CONVERSION AND MANAGEMENT, 2021, 238
[9]   Two-evaporator refrigeration system integrated with expander-compressor booster [J].
Erdinc, Mehmet Tahir .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 154 :349-363
[10]   Experimental investigation of multi-ejector CO2 heat pump system with and without IHX [J].
Guruchethan, A. M. ;
Reddy, Y. Siva Kumar ;
Maiya, M. P. ;
Hafner, Armin .
ENERGY, 2024, 297