Shipboard Medium-Voltage DC Integrated Power System Ⅱ: Protection and Fault Management Technology

被引:0
|
作者
Yang, Yayu [1 ,2 ]
Tai, Nengling [2 ,3 ]
Huang, Wentao [2 ]
Yu, Moduo [2 ]
Liu, Yu [4 ]
机构
[1] Logistics Engineering College, Shanghai Maritime University, Shanghai,201306, China
[2] Key Laboratory of Control of Power Transmission and Conversion, Ministry of Education, Shanghai Jiao Tong University, Shanghai,200240, China
[3] College of Smart Energy, Shanghai Jiao Tong University, Shanghai,200240, China
[4] School of Information Science and Technology, ShanghaiTech University, Shanghai,201210, China
关键词
Transient analysis;
D O I
10.19595/j.cnki.1000-6753.tces.231646
中图分类号
学科分类号
摘要
The shipboard medium-voltage DC (MVDC) integrated power system (IPS) is the technological development direction of the shipboard IPS. As the second part, this paper focuses on the protection and fault management technology of the shipboard MVDC IPS, which includes four parts: fault characteristics analysis, protection principle, fault isolation scheme and reconfiguration method. First of all, the special technical requirements for the protection and fault management technology are analyzed. The shipboard MVDC IPS has high requirements for selectivity and speed. The protection and fault management scheme needs to fully consider the shipboard multiple operating modes and the transient response of multi-type power electronic converters. Then, the fault characteristics analysis method and the protection principle are summarized, and the limitations are outlined. Subsequently, the fault isolation scheme and reconfiguration method are comprehensive reviewed, and the detailed comparisons are made respectively. Finally, the future research trends of the protection and fault management technology of the shipboard MVDC IPS are pointed out. 1) Fault characteristics analysis. The fault transient characteristics analysis methods based on time-frequency domain transformation, nodal impedance matrix analysis, topology simplification, and pole-mode transformation analysis in multi-terminal DC (MTDC) transmission and distribution system provide important references for the shipboard MVDC IPS. However, the fault characteristic analysis model of the complex topology shipboard MVDC IPS containing multi-type power electronic converters, multiple system nodes and multiple operating modes still needs to be studied. 2) Protection principle. Intelligent protection methods require a large amount of training data, which limits the engineering applications. The shipboard MVDC IPS protection can draw on the existing MTDC transmission and distribution system protection method to a certain extent. However, due to the short ship cables, inconsistent DC line boundaries, multiple system nodes, and complex topology, more detailed and in-depth research is still needed. 3) Fault isolation scheme. The hybrid DC circuit breaker (DCCB) has the advantages of low on-state loss of mechanical DC circuit breaker (MCB) and fast breaking speed of solid-state DCCB, which is one of the main technological development directions of DCCB. Currently, the fault isolation scheme based on inductive DC fault current limiter (DCFCL) and DCCB is more suitable for the shipboard MVDC IPS. The simple topology and low cost-based current-limiting DCCB and the high reliability multi-port DCCB are the future research directions. 4) Reconfiguration method. Combining the advantages of centralized manner-based reconfiguration methods and distributed reconfiguration methods, the muti-level distributed reconfiguration method is a meaningful research direction. What is more, the objective function and constraints of the shipboard MVDC IPS reconfiguration method require further study. © 2024 China Machine Press. All rights reserved.
引用
收藏
页码:7341 / 7364
相关论文
共 50 条
  • [31] Cost-effective secondary voltage control in dc shipboard integrated power system
    Shi, Tianling
    Wang, Fei
    Zhang, Shengqi
    Liu, Heyu
    Li, Li
    IET POWER ELECTRONICS, 2024, 17 (16) : 2642 - 2655
  • [32] Control and Operation of Medium-voltage High-power Bi-directional Resonant DC-DC Converters in Shipboard DC Distribution Systems
    Dong, Dong
    Garces, Luis
    Agamy, Mohammed
    Pan, Yan
    Wu, Xinhui
    She, Hongwu
    Xu, He
    Li, Xiaohong
    Dai, Jian
    2016 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2016,
  • [33] Modular Hybrid DC Circuit Breaker for Medium-Voltage DC System
    Kim, Dong-Uk
    Kim, Sungmin
    2020 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2020, : 1312 - 1318
  • [34] Modelling of shipboard medium-voltage direct current system for system level dynamic analysis
    Shi, Jian
    Amgai, Ranjit
    Abdelwahed, Sherif
    IET ELECTRICAL SYSTEMS IN TRANSPORTATION, 2015, 5 (04) : 156 - 165
  • [35] An Unscented Kalman Filter Based Dynamic State Estimation for the Medium-voltage DC Integrated Power System With Pulse Load
    Xiao R.
    Wang G.
    Xu C.
    Hao X.
    Huang R.
    Huang M.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (23): : 7555 - 7565
  • [36] Bayesian Selectivity Technique for Earth Fault Protection in Medium-Voltage Networks
    Elkalashy, Nagy I.
    Elhaffar, Abdelsalam M.
    Kawady, Tamer A.
    Tarhuni, Naser G.
    Lehtonen, Matti
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2234 - 2245
  • [37] Incipient Fault Identification Based Photovoltaic Medium Voltage DC System Protection
    Jia K.
    Shi Z.
    Chen M.
    Chen C.
    Bi T.
    1600, Chinese Society for Electrical Engineering (41): : 8463 - 8474
  • [38] CONSIDERATIONS FOR GROUND FAULT PROTECTION IN MEDIUM-VOLTAGE INDUSTRIAL AND COGENERATION SYSTEMS
    LOVE, DJ
    HASHEMI, N
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1988, 24 (04) : 548 - 553
  • [39] Protection, metering, monitoring, and control of medium-voltage power systems
    Duncan, BK
    Bailey, BG
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2004, 40 (01) : 33 - 40
  • [40] Relay protection schemes on shipboard integrated power system
    Wang, Qi
    Ma, Wei-Ming
    Fu, Li-Jun
    Lu, Hao
    Gaodianya Jishu/High Voltage Engineering, 2007, 33 (10): : 157 - 161